Item

Description

Range

 

Set the number of refreshes to

 

 

secure the send/receive data in

 

 

station units during

 

 

communication.

 

Refresh

(Default: 1time)

1 to 1000times

Interval

Valid when "Secured data send/

 

 

Secured data receive" is marked

 

 

by the control station side network

 

 

parameters of the MELSECNET/H

 

 

network system.

 

 

 

 

 

Set the communication

 

 

transmission speed.

 

Transmission

(Default: 25Mbps)

10Mbps/25Mbps

Speed

When specifying [MNET/10 mode]

 

as the network type, only 10Mbps

 

 

can be set applicable.

 

 

 

 

*1 Cannot be set for the QCPU redundant system.

*2 For details, refer to the following manual.

Q corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)

(2) MELSECNET/10

10.3.3Routing parameter setting

Up to 64 [Transfer Network No.]s can be set.

However, the same transfer network number cannot be set twice or more (multiple times).

Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.

POINT

(1)Routing parameter setting

When communicating within the host network, routing parameter setting is unnecessary.

(2)Selection of communication unit

Routing parameters cannot be set in the GT15- 75J71LP23-Z and the GT15-75J71BR13-Z. When setting routing parameters, use the GT15- J71LP23-25 or the GT15-J71BR13 according to the connection type to be used.

For details of routing parameters, refer to the following manual.

Q corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)

Item

Description

Range

 

Set the number of retries to be

 

 

performed when a communication

 

Retry

timeout occurs.

0 to 5times

When no response is received after

 

 

 

retries, a communication times out.

 

 

(Default: 3times)

 

 

 

 

 

Set the time period for a communication

 

Timeout Time

to time out.

3 to 90sec

 

(Default: 3sec)

 

 

 

 

POINT

(1)When MELSECNET/H communication unit is used When connecting the MELSECNET/H network module to the MELSECNET/10 network system, specify the [MNET/10 mode] as a [Network Type].

(2)Communication interface setting by the Utility The communication interface setting can be changed on the Utility's [Communication Settings] after writing [Communication Settings] of project data.

For details on the Utility, refer to the following manual.

GT User's Manual

(3)SwitchPrecedencesetting of MELSECNET/Hin communicationnetwork module settings [Network parameter] of GX Developer

When settings are made by GT Designer3 or the Utility, the latest setting is effective.

Item

Range

Transfer Network No.

1 to 239

 

 

Relay Network No.

1 to 239

 

 

Relay Station No.

1 to 64

 

 

POINT

Routing parameter setting of relay station

Routing parameter setting is also necessary for the relay station.

For the setting, refer to the following.

10.4 PLC Side Setting

10 - 10

10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

10.3 GOT Side Settings