Parameter setting (when connecting to MELSEC-Q or QS series)

(1)[Network parameter] of GX Developer

(a)Network parameter

 

 

Setting

Item

Set value

necessity at

GOT

 

 

 

 

connection

No. of boards in module

1

 

 

 

 

Start I/O No.*1

0000H

 

Operation setting

(Use default value)

 

 

 

 

Type

Master station (fixed)

 

 

 

 

Mode

Remote net

 

(Ver.2 mode)

 

 

 

 

 

 

All connect count

2

 

 

 

 

Remote input (RX)

X400

 

 

 

 

Remote output (RY)

Y400

 

 

 

 

Remote register (RWr)

D300

 

 

 

 

Remote register (RWw)

D200

 

 

 

 

Special relay (SB)

SB0

 

 

 

 

Special register (SW)

SW0

 

 

 

 

Retry count

 

 

 

 

 

Automatic reconnection

 

 

station count

 

 

 

 

 

Stand by master station No.

(Use default value)

 

PLC down select

 

 

 

 

 

Scan mode setting

 

 

 

 

 

Delay information setting

 

 

 

 

 

Station information setting

Refer to (b)

 

 

 

 

Remote device station initial

 

 

setting

(Use default value)

 

Interrupt setting

 

 

 

 

 

: Necessary : As necessary : Not necessary

*1 When using Q170MCPU, set it according to the system configuration.

(b) Station information setting

• Station information setting of station No.1 (GOT)

 

 

 

 

Setting

Item*1

 

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

connection

Station type

 

Ver.1 intelligent

 

 

device station (fixed)

 

 

 

 

 

 

 

 

Exclusive station count*2

 

Exclusive station 1

 

Reserve/invalid station

 

 

No setting

 

select

 

 

 

 

 

 

 

 

 

 

 

 

Intelligent buffer select

 

(Use default value)

 

(word)

 

 

 

 

 

 

 

 

 

 

 

 

: Necessary

: As necessary

: Not necessary

• Station information setting of station No.2 (GOT)

 

 

Setting

Item*1

Set value

necessity at

GOT

 

 

 

 

connection

Station type

Ver.2 intelligent device

 

station (fixed)

 

 

 

 

 

 

Expanded cyclic setting*2

Single

 

Exclusive station count*2

Exclusive station 1

 

Reserve/invalid station

No setting

 

select

 

 

 

 

 

 

Intelligent buffer select

(Use default value)

 

(word)

 

 

 

 

 

 

: Necessary : As necessary

: Not necessary

*1 When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 2 mode)], [Remote station points] can be set. [Remote station points] is a setting for the remote I/O station. The default value (32 points) must be used on the GOT.

*2 Set the same setting as that of the GOT.

POINT

When changing the network parameter

After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF and then ON or resetting.

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

13 - 21

13.4 PLC Side Setting