15.5 FREQROL Series Inverter Side Settings

For details of the inverter, refer to the manual of each series.

15.5.1Connecting FREQROL-S500, S500E, F500J series

Communication settings

Make the communication settings of the inverter.

Be sure to perform the inverter reset after updating each parameter.

(1) Communication port and corresponding parameters

GOT connection

Parameters corresponding to inverter

destination

 

RS-485 port

Pr.79, n1 to n7, n10 to n12

 

 

(2)Communication settings of inverter

Set the following parameters using the PU (parameter unit). Set Pr.30 (Extended function selection) to 1 [With display] before making the parameter settings.

Do not change these parameters, even though they can be monitored from the GOT. If they are changed, communication with the GOT is disabled.

Setting item*1

Parameter No.*4

Set value

 

Contents of setting

Communication station number

n1 (331)

0 to 31

 

15.5.12 Station number

 

 

setting

 

 

 

 

 

 

 

 

 

Communication speed*2

n2 (332)

192*3

 

19200bps

Stop bit length*2

n3 (333)

10

 

Data length: 7bit

 

Stop bit length: 1bit

 

 

 

 

 

 

 

 

 

Parity check presence/absence*2

n4 (334)

1

 

Odd

Number of communication retries

n5 (335)

---

The inverter will not come to an

(65535)

 

alarm stop.

 

 

 

 

 

 

 

 

Communication check time interval

n6 (336)

---

 

Communication check

 

suspension

 

 

 

 

 

 

 

 

 

Wait time setting

n7 (337)

0

 

0ms

 

 

 

 

 

CRLF selection

n11 (341)

1*3

 

With CR, without LF

Protocol selection*5

 

Operation mode selection

Pr.79

0*3

 

External operation mode at

 

power on

 

 

 

 

 

 

 

 

 

Link start mode selection

n10 (340)

1

 

Computer link operation

 

 

 

 

 

E2PROM write selection

n12 (342)

0*3

 

Written to RAM and EEPROM

*1 Setting items are parameter names described in the manual of FREQROL-S500, S500E, and F500J series.

*2 Settings on the GOT can be changed.

When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.

*3 Inverter default values (No need to change)

*4 When being monitored from the GOT, the parameter n1 through n7 correspond with Pr.331 through Pr.337, and the parameter n10 through n12 correspond with Pr.340 through Pr.342.

Numbers in brackets show the parameter number when the parameter unit is in use.

*5 There is no Protocol selection setting on the inverter side.

9

MELSECNET/H(PLCNETWORK) CONNECTIONPLC TO 10

MELSECNET/10(PLCNETWORK) CONNECTIONPLC TO 11

CONTROLLERIENETWORKCONNECTION Link-CC 12

FIELDIENETWORKCONNECTION Link-CC 13

CONNECTIONLinkDEVICE(INTELLIGENTSTATION) -CC 14

LinkCONNECTIONG4) -CC (Via 15

INVERTER CONNECTION 16

SERVO AMPLIFIERCONNECTION

15. INVERTER CONNECTION

15 - 31

15.5 FREQROL Series Inverter Side Settings