15.5.9Connecting FREQROL-F700PJ series

Communication settings

Make the communication settings of the inverter.

Be sure to perform the inverter reset after updating each parameter.

(1) Communication port and corresponding parameters

GOT connection

Parameters corresponding to inverter

destination

 

PU connector

Pr.79, Pr.117 to Pr.124, Pr.340, Pr.342, Pr.549

 

 

(2)Communication settings of inverter

Set the following parameters using the PU (parameter unit). Set Pr.160 (User group read selection) to 0 [The simple mode and extended parameters can be displayed] before making the parameter settings.

Do not change these parameters, even though they can be monitored from the GOT. If they are changed, communication with the GOT is disabled.

Setting item*1

Parameter No.

Set value

 

Contents of setting

PU communication station number

Pr.117

0 to 31

 

15.5.12 Station number

 

 

setting

 

 

 

 

 

 

 

 

 

PU communication speed*2

Pr.118

192*3

 

19200bps

PU communication stop bit length

Pr.119

10

 

Data length: 7bit

 

Stop bit length: 1bit

 

 

 

 

 

 

 

 

 

PU communication parity check*2

Pr.120

1

 

Odd

Number of PU communication retries

Pr.121

9999

The inverter will not come to an

 

alarm stop.

 

 

 

 

 

 

 

 

 

PU communication check time interval

Pr.122

9999

 

Communication check

 

suspension

 

 

 

 

 

 

 

 

 

PU communication waiting time setting

Pr.123

0

 

0ms

 

 

 

 

 

PU communication CR/LF selection

Pr.124

1*3

 

With CR, without LF

Protocol selection

Pr.549

0*3

 

Mitsubishi inverter protocol

Operation mode selection

Pr.79

0*3

External operation mode at

power on

 

 

 

 

 

 

 

 

Communication startup mode selection

Pr.340

1

 

Network operation mode.

 

 

 

 

 

Communication EEPROM write selection

Pr.342

0*3

 

Written to RAM and EEPROM

*1 Setting items are parameter names described in the manual of FREQROL-F700 series.

*2 Settings on the GOT can be changed.

When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.

*3 Inverter default values (No need to change)

HINT

Automatic setting with Pr.999

If Pr.999 is set as the following, the communication settings other than [PU communication station number] and [Communication EEPROM write selection] can be automatically set in a batch to the default communication settings of the GOT side.

 

Parameter No.

Set value

Description

Operation in parameter setting mode

 

 

Pr.999*1

 

10

GOT Initial settings (PU connector)

[AUTO] [GOT] [1]Write

 

*1

When monitoring the value of Pr.999, 9999 is always monitored.

 

 

 

 

 

 

 

15 - 40

15. INVERTER CONNECTION

 

15.5 FREQROL Series Inverter Side Settings