12.3 GOT side settings

12.3.1Setting communication interface (Communication settings)

Set the channel of connecting equipment.

2.

3.

4.

Click!

1. Select [Common] [Controller Setting] from the menu.

2. The Controller Setting window is displayed. Select the channel to be used from the list menu.

3. Set the following items.

Manufacturer: Mitsubishi

Controller Type: Set according to the Controller Type to be connected.

I/F: Interface to be used

Driver: CC-Link IE Field Network

4.The detailed setting is displayed after Manufacturer, Controller Type, I/F, and Driver are set.

Make the settings according to the usage environment.

12.3.2 Communication detail settings

Click the [OK] button when settings are completed.

POINT

The settings of connecting equipment can be confirmed in [I/F Communication Setting]. For details, refer to the following.

1.1.2 I/F communication setting

12.3.2Communication detail settings

Make the settings according to the usage environment.

Item

Description

Range

Network

Set the network Type

• CC IE Field

Type*4

 

 

Network No.

Set the network No. of the GOT.

1 to 239

(Default: 1)

 

 

 

 

 

Station No.

Set the station No. of the GOT.

1 to 120

(Default: 1)

 

 

 

 

 

 

 

• Online

 

Set the operation mode of the GOT.

• Offline

Mode Setting

(Default:

• H/W test*1

 

Online (auto. reconnection))

Self-loopback

 

 

test*1

 

Set the number of refreshes to

 

Refresh

secure the send/receive data in

1 to 1000ms

Interval

station units during communication.

 

(Default: 25ms)

 

 

 

 

 

Set the hold/clear of input from the

 

Input for Error

station where the data link is faulty

 

due to some reason such as turning

Clear/Hold

Station

the power OFF.

 

 

 

 

(Default: Clear)

 

 

 

 

 

Set the number of retries to be

 

 

performed when a communication

 

 

timeout occurs.

 

Retry

When receiving no response after

0 to 5times

 

retries, the communication times

 

 

out.

 

 

(Default: 3times)

 

 

 

 

Timeout

Set the time period for a

 

communication to time out.

3 to 90sec

Time

(Default: 3sec)

 

 

 

 

 

 

 

Set the delay time for reducing the

 

Delay Time

load of the network/destination PLC.

0 to 300ms

 

(Default: 0ms)

 

 

 

 

 

Set the monitor speed for the CC-

 

Monitor

Link IE field network.

 

This setting is not valid in all

High*2/Normal/Low*3

Speed

systems.

 

 

 

 

(Default: High)

 

(Continued to next page)