Parameter setting (when connecting to C Controller module)

Use SW3PVC-CCPU-E Ver.3.05F or later for the MELSECNET/H utility.

(1) Connection settings

 

 

Setting

Item

Set value

necessity at

 

 

GOT connection

Target module*1

192.168.3.3 (Default)

 

Write authority

Mark the checkbox

 

 

 

 

User name*2

target

 

Password*2

password

 

Detailed settings

-

 

 

 

 

: Necessary : As necessary : Not necessary

*1 If the IP address of the C Controller module has been changed, input the changed IP address or host name.

*2 If the account of the C Controller module has been changed, input the changed user name and password.

(2)MELSECNET/H Utility's [Parameter Settings]

(a)Parameter settings

 

 

Setting

Item

Set value

necessity at

 

 

GOT connection

Number of modules

1

 

 

 

 

Link device refresh cycle

(Use default value)

 

 

 

 

Routing parameter

Refer to (b).

 

 

 

 

Target module

1

 

 

 

 

Start I/O No.

0000H

 

 

 

 

Channel No.

(Use default value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

 

Item

 

 

 

 

Set value

necessity at

 

 

 

 

 

 

GOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

Network type

 

 

 

 

MNET/10 mode

 

settings

 

 

 

 

(Control station)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network No.*1

 

 

 

 

1

 

 

 

 

 

 

 

Operation

Group No.

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

Online

 

 

 

 

 

 

 

 

 

 

 

 

 

Return

 

 

 

 

 

 

 

(Use default value)

 

 

 

 

 

 

 

 

 

 

 

Refresh parameters

 

 

 

 

(Use default value)

 

 

 

 

 

 

 

 

 

 

 

 

Total stations

 

 

 

 

2

 

 

 

 

 

 

 

 

Assignment method

 

 

Start/End

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for

LB

 

Sta.

 

Start

 

0000H

 

 

 

 

 

 

 

 

 

assignmentrangeNetwork

settingsLB/LW

rangeSendforrangeSend

stationeachLWstationeach

 

No.1

 

End

 

00FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*2

 

 

 

Sta.

 

Start

 

0100H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.2

 

End

 

01FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sta.

 

Start

 

0000H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.1

 

End

 

00FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sta.

 

Start

 

0100H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.2

 

End

 

01FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(LX/LY) settings*2

 

 

No setting

 

 

Monitoring time

 

 

 

 

(Use default value)

 

 

 

 

 

 

 

Specify I/O master Sta.*2

 

No setting

 

 

Specify reserved Sta.

 

 

No setting

 

 

 

 

 

 

 

 

Supplementary settings

 

 

(Use default value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Necessary

: As necessary : Not necessary

*1 Specify the same network No. as that of the GOT.

*2 Be sure to set the setting to perform the cyclic transmission.

POINT

When changing the network parameter

After writing the network parameter to the C Controller module, either turn the C Controller module OFF and then ON or reset it.

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

10 - 15

10.4 PLC Side Setting