*1 To connect the GOT with the Ethernet module (Q Series) in the one-on-one relationship using a cross cable, set [Timeout Time] to 6sec. or longer.

*2 Click the [Setting] button and perform the setting in the [GOT IP Address Setting] screen.

GT15

Item

Description

Range

GOT NET No.

Set the network No. of the GOT.

1 to 239

(Default: 1)

 

 

 

 

 

GOT PLC No.

Set the station No. of the GOT.

1 to 64

(Default: 1)

 

 

 

 

 

GOT

Set the IP address of the GOT.

0.0.0.0 to

IP address

(Default: 192.168.0.18)

255.255.255.255

 

 

 

 

Set the subnet mask for the sub

 

 

network.(Only for connection via

 

Subnet

router)

0.0.0.0 to

Mask

If the sub network is not used, the

255.255.255.255

 

default value is set.

 

 

(Default: 255.255.255.0)

 

 

 

 

 

Set the router address of the default

 

Default

gateway where the GOT is

0.0.0.0 to

connected.(Only for connection via

Gateway

255.255.255.255

router)

 

 

 

(Default: 0.0.0.0)

 

 

 

 

Ethernet

Set the GOT port No. for Ethernet

1024 to 5010,

5014 to 65534

Download

download.

(Except for 5011, 5012,

Port No.

(Default: 5014)

5013 and 49153)

 

 

 

 

 

 

Set the GOT port No. for the

 

 

connection with the Ethernet module.

1024 to 5010,

GOT

• For Ethernet (MELSEC), Q17nNC,

5014 to 65534

Communication

and CRnD-700

(Except for 5011, 5012,

Port No.

(Default: 5001)

5013 and 49153)

 

• For Ethernet(FX), Gateway

 

 

 

(Default: 5019)

 

 

 

 

 

Set the number of retries to be

 

 

performed when a communication

 

Retry

timeout occurs.

0 to 5times

When receiving no response after

 

 

 

retries, the communication times out.

 

 

(Default: 3times)

 

 

 

 

 

Specify the time period from the GOT

 

Startup Time

startup until GOT starts the

3 to 255sec

communication with the PLC CPU.

 

 

 

(Default: 3sec)

 

 

 

 

Timeout Time

Set the time period for a

 

communication to time out.

3 to 90sec

*1

(Default: 3sec)

 

 

 

 

 

 

Delay

Set the delay time for reducing the

0 to 10000

load of the network/destination PLC.

Time

( 10ms)

(Default: 0ms)

 

 

 

 

 

*1 To connect the GOT with the Ethernet module (Q Series) in the one-on-one relationship using a cross cable, set [Timeout Time] to 6sec. or longer.

8 - 16

8. ETHERNET CONNECTION

 

8.3 GOT Side Settings