Setting necessity

Item

 

Set value

at GOT

 

 

 

connection

Communication data code

 

 

 

 

(Use default value)

 

Enable online change

 

 

 

 

 

(MC protocol)

 

 

 

 

 

 

 

Open settings

 

Refer to (2)

 

 

 

 

 

 

: Necessary : As necessary

: Not necessary

(2)Open settings

The setting is required for all the connected GOTs.

Item

Set value

Protocol

UDP (fixed)

 

 

Open system

MELSOFT connection (fixed)

 

 

Host station port No.

-

 

 

[Controller Setting] and [Ethernet] of GT Designer3

POINT

(1)[Controller Setting] and [Ethernet] of GT Designer3

For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.

8.3.1 Setting communication interface (Communication settings)

(2)Ethernet setting

The settings items for the network No. and station

No. do not exist at the Built-in Ethernet port Motion Controller CPU side. However, these virtual values must be set on the GOT side.

Therefore, set the network No. and station No. on the GOT side. Set the network No. that is not existed on the network system and any station No..

(3) Controller setting

Item

Setting (Use default value.)

GOT NET No.

1

 

 

GOT PC No.

1

 

 

GOT IP Address

192.168.3.1

 

 

GOT Port No. (Communication)

5001

 

 

GOT Port No.

5014

(Ethernet Download)

 

 

 

Default Gateway

0.0.0.0

 

 

Subnet Mask

255.255.255.0

 

 

Retry

3times

 

 

Startup Time

3 sec

 

 

Timeout time

3 sec

 

 

Delay Time

0ms

 

 

(4) Ethernet setting

 

Item

Set value

 

 

Host

*

 

 

 

 

 

 

N/W No.

1*1

Ethernet

 

PC No.

2*2

 

Type

QnUDE(H)

setting No.1

 

 

 

 

 

 

IP address

192.168.3.39*3

 

 

Port No.

5006 (fixed)

 

 

 

 

 

 

Communication

UDP (fixed)

 

 

 

 

*1 Set the same value as that of GOT N/W No.

*2 Set a value different from that of GOT PLC No.

*3 Set it to the IP address value of the Built-in Ethernet port Motion Controller CPU side.

Checking communication state of Connecting to Built-in Ethernet port CPU

(1)When using the Command Prompt of Windows® Execute a Ping command at the Command Prompt of Windows®.

(a)When normal communication C:\>Ping 192.168.3.39

Reply from 192.168.3.2: bytes=32 time <10ms TTL=32

(b)When abnormal communication C:\>Ping 192.168.3.39 Request timed out.

(2)When abnormal communication

At abnormal communication, check the followings and execute the Ping command again.

• Cable connecting condition

• Confirmation of switch and network parameter setting

• Operation state of PLC CPU (faulty or not)

• The IP address of Built-in Ethernet port CPU specified in the Ping command

1

PREPARATORYFORPROCEDURESMONITORING 2

RANGESETBE

DEVICE CANTHAT 3

RANGEACCESS MONITORINGFOR 4

MONITORTOREDUNTANTSYSTEM HOW 5

CONNECTIONBUS 6

DIRECTTOCONNECTIONCPU 7

LINKCOMPUTER CONNECTION 8

ETHERNETCONNECTION

8. ETHERNET CONNECTION

8 - 47

8.4 PLC Side Setting