(2)Open settings

The setting is required for all the connected GOTs.

Item

Set value

Protocol

UDP (fixed)

 

 

Open system

MELSOFT connection (fixed)

 

 

Host station port No.

(Use default value)

 

 

[Controller Setting] and [Ethernet] of GT Designer3

POINT

(3)[Controller Setting] and [Ethernet] of GT Designer3

For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.

8.3.1 Setting communication interface (Communication settings)

(4)Ethernet setting

When connecting Built-in Ethernet port CPU to a GOT, the settings items for the network No. and station No. do not exist at the PLC side. However, these virtual values must be set on the GOT side. Therefore, set the network No. and station No. Set the network No. that is not existed on the network system and any station No..

(1)Controller setting

Item

Set value (Use default value)

GOT NET No.

1

 

 

GOT PLC No.

1

 

 

GOT IP Address

192.168.0.18

 

 

GOT Port No. (Communication)

5001

 

 

GOT Port No.

5014

(Ethernet Download)

 

 

 

Default Gateway

0.0.0.0

 

 

Subnet Mask

255.255.255.0

 

 

Retry

3times

 

 

Startup Time

3sec

 

 

Timeout Time

3sec

 

 

Delay Time

0ms

 

 

(2) Ethernet setting

 

Item

 

 

Set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Host

*

 

-

 

 

 

 

 

 

 

 

 

 

 

 

N/W No.

1*1

1*1

 

 

PLC No.

2*2

3*2

Ethernet setting

Type

QnUDE(H),

QnUDE(H),

No.1

 

LCPU

LCPU

 

 

 

 

 

 

 

 

 

 

 

 

 

IP address

192.168.0.1

192.168.0.2

 

 

 

 

 

 

 

 

 

 

 

Port No.

5006 (fixed)

5006 (fixed)

 

 

 

 

 

 

 

 

 

 

 

Communication

UDP (fixed)

UDP (fixed)

 

 

 

 

 

 

 

 

 

*1 Set the same value as that of GOT N/W No.

*2 Set a value different from that of the GOT PLC No. and the PLC No. of other PLCs on the same network.

1

PREPARATORYFORPROCEDURESMONITORING 2

RANGESETBE

DEVICE CANTHAT 3

RANGEACCESS MONITORINGFOR 4

MONITORTOREDUNTANTSYSTEM HOW 5

CONNECTIONBUS 6

DIRECTTOCONNECTIONCPU 7

LINKCOMPUTER CONNECTION 8

ETHERNETCONNECTION

8. ETHERNET CONNECTION

8 - 23

8.4 PLC Side Setting