(3)Monitoring target change when system switching occurs in a redundant system
(a)System switching due to an alarm occurred in the control system
When system switching occurs, the
The
Since the GOT monitors the master station, the monitoring target is automatically changed to the new control system after system switching.
(b)System switching due to a network communication error occurred in other than the
When system switching occurs, the
The
Since the GOT monitors the master station, the monitoring target is not automatically changed to the new control system after system switching.
To automatically change the monitoring target of the GOT to the new control system after system switching, switch the data link control from the standby master station to the master station by the sequence program of the new control system.
For details of the sequence program, refer to the following manual.
QnPRHCPU User's Manual (Redundant System) (Sample Programs when Using
POINT
To automatically change the monitoring target in the QCPU redundant system when using the
For details of using the
QnPRHCPU User's Manual (Redundant System)