11.3 GOT side settings
Set the channel of connecting equipment.
2.
3.
4.
Click!
1. Select [Common] [Controller Setting] from the menu.
2. The Controller Setting window is displayed. Select the channel to be used from the list menu.
3. Set the following items.
•Manufacturer: Mitsubishi
•Controller Type: Set according to the Controller Type to be connected.
•I/F: Interface to be used
•Driver:
4.The detailed setting is displayed after Manufacturer, Controller Type, I/F, and Driver are set.
Make the settings according to the usage environment.
11.3.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
The settings of connecting equipment can be confirmed in [I/F Communication Setting]. For details, refer to the following.
Make the settings according to the usage environment.
Item | Description | Range | |
Network | Set the network Type | • CC IE Control | |
• CC IE Control | |||
Type*4 | (Default: CC IE Control) | ||
extended mode | |||
|
| ||
|
|
| |
Network No. | Set the network No. | 1 to 239 | |
(Default: 1) | |||
|
| ||
|
|
| |
Station No. | Set the station No. of the GOT. | 1 to 120 | |
(Default: 1) | |||
|
| ||
|
|
| |
|
| • Online | |
|
| (auto. | |
|
| reconnection) | |
|
| • Offline | |
| Set the operation mode of the GOT. | • Test station*1 | |
| • | ||
Mode Setting | (Default: | ||
test*1 | |||
| Online (auto. reconnection)) | ||
|
| • Internal self- | |
|
| loopback test*1 | |
|
| • Line test*1 | |
|
| • H/W test*1 | |
| Set the number of retries to be |
| |
| performed when a communication |
| |
Retry | timeout occurs. | 0 to 5times | |
When no response is received after | |||
| retries, a communication times out. |
| |
| (Default: 3times) |
| |
|
|
| |
Timeout | Set the time period for a |
| |
communication to time out. | 3 to 90sec | ||
Time | |||
(Default: 3sec) |
| ||
|
| ||
|
|
| |
| Set the delay time for reducing the |
| |
Delay Time | load of the network/destination PLC. | 0 to 300ms | |
| (Default: 0ms) |
| |
|
|
| |
| Set the number of refreshes to |
| |
| secure the send/receive data in |
| |
| station units during communication. |
| |
Refresh | (Default: 1ms) |
| |
Valid when [Block data assurance | 1 to 1000ms | ||
Interval | |||
per station is available.] is checked |
| ||
|
| ||
| by the control station side network |
| |
| parameters of the |
| |
| Controller Network. |
| |
|
|
|