(b)Routing parameter setting

Up to 64 [Transfer Network No.]s can be set. However, the same transfer network number cannot be set twice or more (multiple times).

Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.

Item

Range

Transfer target network No.

1 to 239

 

 

Relay network No.

1 to 239

 

 

Relay station No.

1 to 120

 

 

POINT

Routing parameter setting of request source

Routing parameter setting is also necessary for the request source GOT.

For the setting, refer to the following. 10.3.3 Routing parameter setting

[Controller Setting] of GT Designer3

Item

Set value (Use default)

Retry

3times

 

 

Timeout Time

3sec

 

 

POINT

[Controller Setting] of GT Designer3

For the setting method of [Controller Setting] of GT Designer3, refer to the following.

10.3.1 Setting communication interface (Communication settings)

Setting of the MELSECNET/10 communication unit

Item

Set value

Network number setting switch

1: Network No.1

 

 

Group number setting switch

0: No group setting (fixed)

 

 

Station number setting switch

2: Station No.2

 

 

Mode setting switch

0: Online (fixed)

 

 

POINT

Setting of the MELSECNET/10 communication unit

For the setting method of the MELSECNET/10 communication unit, refer to the following.

10.3.1 Setting communication interface (Communication settings)

10 - 16

10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

 

10.4 PLC Side Setting