(b)Routing parameter setting
Up to 64 [Transfer Network No.]s can be set. However, the same transfer network number cannot be set twice or more (multiple times).
Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.
Item | Range |
Transfer target network No. | 1 to 239 |
|
|
Relay network No. | 1 to 239 |
|
|
Relay station No. | 1 to 120 |
|
|
POINT
Routing parameter setting of request source
Routing parameter setting is also necessary for the request source GOT.
For the setting, refer to the following. 10.3.3 Routing parameter setting
[Controller Setting] of GT Designer3
Item | Set value (Use default) |
Retry | 3times |
|
|
Timeout Time | 3sec |
|
|
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT Designer3, refer to the following.
10.3.1 Setting communication interface (Communication settings)
Setting of the MELSECNET/10 communication unit
Item | Set value |
Network number setting switch | 1: Network No.1 |
|
|
Group number setting switch | 0: No group setting (fixed) |
|
|
Station number setting switch | 2: Station No.2 |
|
|
Mode setting switch | 0: Online (fixed) |
|
|
POINT
Setting of the MELSECNET/10 communication unit
For the setting method of the MELSECNET/10 communication unit, refer to the following.
10.3.1 Setting communication interface (Communication settings)
10 - 16 | 10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK) |
| 10.4 PLC Side Setting |