Item | Description | Range | |
GOT | Set the IP address of the GOT. | 0.0.0.0 to | |
IP Address | (Default: 192.168.3.18) | 255.255.255.255 | |
|
|
| |
IP Label | Set the IP Label of detail setting. | - | |
|
|
| |
| Set the subnet mask for the sub |
| |
| network. (Only for connection via |
| |
Subnet Mask*1 | router) | 0.0.0.0 to | |
If the sub network is not used, | 255.255.255.255 | ||
| |||
| the default value is set. |
| |
| (Default: 255.255.255.0) |
| |
|
|
| |
| Set the router address of the |
| |
Default | default gateway where the GOT | 0.0.0.0 to | |
is connected. (Only for | |||
Gateway*1 | 255.255.255.255 | ||
connection via router) | |||
|
| ||
| (Default: 0.0.0.0) |
| |
|
|
| |
Ethernet | Set the GOT port No. for | 1024 to 5010, | |
5014 to 65534 | |||
Download Port | Ethernet download. | ||
(Except for 5011, 5012, | |||
No.*1 | (Default: 5014) | ||
5013, 49153) | |||
|
| ||
|
|
|
*1 Click the [Setting] button and perform the setting in the [GOT IP Address Setting] screen.
POINT
Setting the FA transparent function of GX Works2
When connecting the GOT and the personal computer in Ethernet connection, set the GOT IP address and the Ethernet download port No. to the same as the contents of PLC side I/F detailed setting of GOT.
(c)Host (modem) setting
When communicating the GOT via modem, set the interface of the GOT to be used in the communication with the modem.
Item | Description | Range | |
| Set this item when change the | 9600bps, | |
Transmission | transmission speed used for | 19200bps, | |
communication with the connected | 38400bps, | ||
Speed | |||
equipment. | 57600bps, | ||
| |||
| (Default: 115200) | 115200bps | |
|
|
| |
| Set this item when change the data |
| |
Data Bit | length used for communication with | 7bits/8bits | |
the connected equipment. | |||
|
| ||
| (Default: 8bit) |
| |
|
|
| |
| Specify the stop bit length for |
| |
Stop Bit | communications. | 1bit/2bits | |
| (Default: 1bit) |
| |
|
|
|
Item | Description | Range | |
| Specify whether or not to perform a | None | |
| parity check, and how it is performed | ||
Parity | Even | ||
during communication. | |||
| Odd | ||
| (Default: Odd) | ||
|
| ||
|
|
| |
| Set the number of retries to be |
| |
Retry | performed when a communication | 1time | |
timeout occurs. | |||
|
| ||
| (Default: 1time) |
| |
|
|
| |
| Set the time period for a |
| |
Timeout Time | communication to time out. | 5sec | |
| (Default: 5sec) |
| |
|
|
| |
Initialization | Set the AT command to initialize the | Up to 255 | |
modem. | |||
alphanumeric | |||
Command*1 | (Default: | ||
characters | |||
| AT&FE0%C0&K0&D0W2S0=1) | ||
|
| ||
|
|
|
*1 The maximum number of characters of the AT command differs according to the specification of the modem. When the maximum number of characters of the AT command which can be used in the modem is less than 255, set the initialization command according to the specification of the modem.
3. Click the [OK] button when settings are completed.
POINT
(1)Communication interface setting by Utility The communication interface setting can be changed on the Utility's [Communication Settings] after downloading [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GT User's Manual
(2)Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
17
ROBOT CONTROLLER CONNECTION
18
CNC CONNECTION
19
CONNECTION
GOT
20
21
FUNCTION
22
FUNCTION
FA TRANSPARENT
22. FA TRANSPARENT FUNCTION | 22 - 37 |