Item

Description

Range

GOT

Set the IP address of the GOT.

0.0.0.0 to

IP Address

(Default: 192.168.3.18)

255.255.255.255

 

 

 

IP Label

Set the IP Label of detail setting.

-

 

 

 

 

Set the subnet mask for the sub

 

 

network. (Only for connection via

 

Subnet Mask*1

router)

0.0.0.0 to

If the sub network is not used,

255.255.255.255

 

 

the default value is set.

 

 

(Default: 255.255.255.0)

 

 

 

 

 

Set the router address of the

 

Default

default gateway where the GOT

0.0.0.0 to

is connected. (Only for

Gateway*1

255.255.255.255

connection via router)

 

 

 

(Default: 0.0.0.0)

 

 

 

 

Ethernet

Set the GOT port No. for

1024 to 5010,

5014 to 65534

Download Port

Ethernet download.

(Except for 5011, 5012,

No.*1

(Default: 5014)

5013, 49153)

 

 

 

 

 

*1 Click the [Setting] button and perform the setting in the [GOT IP Address Setting] screen.

POINT

Setting the FA transparent function of GX Works2

When connecting the GOT and the personal computer in Ethernet connection, set the GOT IP address and the Ethernet download port No. to the same as the contents of PLC side I/F detailed setting of GOT.

22.6.2 Accessing by GX Works2

(c)Host (modem) setting

When communicating the GOT via modem, set the interface of the GOT to be used in the communication with the modem.

Item

Description

Range

 

Set this item when change the

9600bps,

Transmission

transmission speed used for

19200bps,

communication with the connected

38400bps,

Speed

equipment.

57600bps,

 

 

(Default: 115200)

115200bps

 

 

 

 

Set this item when change the data

 

Data Bit

length used for communication with

7bits/8bits

the connected equipment.

 

 

 

(Default: 8bit)

 

 

 

 

 

Specify the stop bit length for

 

Stop Bit

communications.

1bit/2bits

 

(Default: 1bit)

 

 

 

 

Item

Description

Range

 

Specify whether or not to perform a

None

 

parity check, and how it is performed

Parity

Even

during communication.

 

Odd

 

(Default: Odd)

 

 

 

 

 

 

Set the number of retries to be

 

Retry

performed when a communication

1time

timeout occurs.

 

 

 

(Default: 1time)

 

 

 

 

 

Set the time period for a

 

Timeout Time

communication to time out.

5sec

 

(Default: 5sec)

 

 

 

 

Initialization

Set the AT command to initialize the

Up to 255 one-byte

modem.

alphanumeric

Command*1

(Default:

characters

 

AT&FE0%C0&K0&D0W2S0=1)

 

 

 

 

 

*1 The maximum number of characters of the AT command differs according to the specification of the modem. When the maximum number of characters of the AT command which can be used in the modem is less than 255, set the initialization command according to the specification of the modem.

3. Click the [OK] button when settings are completed.

POINT

(1)Communication interface setting by Utility The communication interface setting can be changed on the Utility's [Communication Settings] after downloading [Communication Settings] of project data.

For details on the Utility, refer to the following manual.

GT User's Manual

(2)Precedence in communication settings

When settings are made by GT Designer3 or the Utility, the latest setting is effective.

17

ROBOT CONTROLLER CONNECTION

18

CNC CONNECTION

19

CONNECTION

GOT MULTI-DROP

20

MULTIPLE-GT14, GT12, GT11, GT10 CONNECTION FUNCTION

21

FUNCTION

MULTI-CHANNEL

22

FUNCTION

FA TRANSPARENT

22. FA TRANSPARENT FUNCTION

22 - 37

22.5 GOT Side Settings