Parameter setting (when connecting to C Controller module)

Use SW3PVC-CCPU-E Ver.3.05F or later for the CC- Link utility.

(1) Connection settings

 

 

Setting

Item

Set value

necessity at

 

 

GOT connection

Target module*1

192.168.3.3 (Default)

 

Write authority

Mark the checkbox

 

 

 

 

User name*2

target

 

Password*2

password

 

Detailed settings

-

 

 

 

 

: Necessary : As necessary : Not necessary

*1 If the IP address of the C Controller module has been changed, input the changed IP address or host name.

*2 If the account of the C Controller module has been changed, input the changed user name and password.

(2)CC-Link Utility's [Parameter Settings]

(a)Parameter settings

 

 

 

 

Setting

 

Item*1

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

connection

Number of modules

 

1

 

 

 

 

 

Target module

 

1

 

 

 

 

 

Start I/O No.

 

0000H

 

 

 

 

 

Channel No.

 

(Use default value)

 

 

 

 

 

 

 

Type

 

Master station (fixed)

 

 

 

 

 

 

 

Mode

 

Remote net

 

 

 

(Ver.1 mode)

 

settings

 

 

 

 

 

 

 

Expanded cyclic setting

Single

 

 

 

 

 

 

 

 

Operation

Occupied number

 

Exclusive station 1

 

 

 

 

 

status

 

 

 

 

Error event: input data

 

Clear

 

 

 

 

 

 

 

 

 

 

CPU stop: data link status

Refresh

 

 

 

 

 

 

 

Other settings

 

(Use default value)

 

 

 

 

 

 

 

All connect count

 

1

 

settings

 

 

 

 

Station Type

Sta.

Intelligent device

 

 

 

 

No.1

station

 

 

 

 

information

 

 

 

 

Reserve/invalid

Sta.

 

 

 

Occupied number*2

Sta.

Exclusive station 1

 

 

 

No.1

 

 

Station

station select

No.1

No setting

 

 

 

 

 

 

 

Intelligent buffer select

 

(Use default value)

 

 

(word)

 

 

 

 

 

 

 

 

 

 

 

 

: Necessary : As necessary : Not necessary

*1 When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 1 mode)], [Remote station points] cannot be set.

*2 Set the same number of occupied stations as that on the GOT.

POINT

When changing the network parameter

After writing the network parameter to the C Controller module, either turn the C Controller module OFF and then ON or reset it.

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

13 - 15

13.4 PLC Side Setting