(c)Routing parameter setting

Up to 64 [Transfer Network No.]s can be set. However, the same transfer network number cannot be set twice or more (multiple times).

Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.

Parameter setting (when connecting to C Controller module)

Use SW3PVC-CCPU-E Ver.3.05F or later for the CC IE Control utility.

(1)Connection settings between personal computer and C controller module

Item

Range

Target network No.

1 to 239

 

 

Relay network No.

1 to 239

 

 

Relay station No.

1 to 120

 

 

POINT

Routing parameter setting of request source

Routing parameter setting is also necessary for the request source GOT.

For the setting, refer to the following. 11.3.3 Routing parameter setting

 

 

Setting

Item

Set value

necessity at

GOT

 

 

 

 

connection

Target module*1

192.168.3.3 (Default)

 

Write authority

Mark the checkbox

 

 

 

 

User name*2

target

 

Password*2

password

 

Detailed settings

-

 

 

 

 

: Necessary : As necessary

: Not necessary

*1 If the IP address of the C Controller module has been changed, input the changed IP address or host name.

*2 If the account of the C Controller module has been changed, input the changed user name and password.

11 - 12

11. CC-Link IE CONTROLLER NETWORK CONNECTION

 

11.4 PLC Side Setting