8.4.10Connecting to PERIPHERAL I/F (Built-in Ethernet port Motion Controller CPU)

This section describes the settings of the GOT and Built-in Ethernet port Motion Controller CPU in the following case of system configuration.

POINT

(1)GOT type setting

For details, refer to the following.

1.1.1 Setting connected equipment (Channel setting)

(2)Setting [Controller Type]

(2)CPU No. specification of Q170MCPU

Set whether to monitor the PLC CPU area or the Motion CPU area of Q170MCPU, in the CPU No. specification. For details, refer to the following.

8.5 Precautions

(3)PLC type of GX Works2/GX Developer

When creating a program, set the following PLC type:

For Q173D(S)CPU/Q172D(S)CPU QnUD(E)(H)CPU

For Q170MCPU Q03UDCPU

(4)Built-in Ethernet port CPU

For details of Built-in Ethernet port CPU, refer to the following manual.

User's Manual of Q173D(S)CPU/

Q172D(S)CPU and Q170MCPU

System configuration

Leave the Built-in Ethernet port Motion Controller CPU settings as default in the following system configuration.

[Controller Setting] and [Ethernet] of GT Designer3

<GOT>

(The settings other than the following are set to the default)

Network No.

: 1

PLC No.

: 1

IP address

: 192.168.3.1

Port No.

: 5001

Communication : UDP (fixed) format

<Connecting to Built-in Ethernet port CPU> *1 (The following settings are set to the default)

Network No.

: 1 (virtual)*2

PLC No.

: 2 (virtual)*2

IP address

: 192.168.3.39

Open system

: MELSOFT connection (fixed)

*1 For the settings when using system devices including a hub and a transceiver, refer to the following.

8.4.2 Connecting to Built-in Ethernet port CPU (multiple connection)

*2 These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.

[Controller Setting] and [Ethernet] of GT Designer3

Basic setting of MT Works2

Use the default values of the basic setting for the system configuration above.

(1) Built-in Ethernet port

 

 

 

Setting necessity

 

Item

Set value

at GOT

 

 

 

connection

 

IP address

192.168.3.39

 

 

(Default)

 

 

 

 

 

 

 

 

 

Subnet mask pattern

-

 

 

 

 

 

 

Default router IP address

-

 

 

 

 

 

 

 

 

 

8 - 46

8. ETHERNET CONNECTION

 

8.4 PLC Side Setting