12.4 PLC Side Setting
This section describes the settings of the GOT and CC- Link IE controller network module in the following case of system configuration.
POINT
For details of the
System configuration (Network Type: CC IE Field)
■ GT Designer3 [Communication setting] of System configuration1 (Network Type: CC IE Field)
<GOT>
(Use the default value for settings other
|
|
|
| than the following.) |
| |
|
|
|
| Network type | : CC IE Field | |
|
|
|
| Network No. | : 1 | |
|
|
|
| Station No. | : 1 | |
|
|
|
| Mode Setting | : Online | |
|
|
|
| Network Configuration Settings : RX/RY00 to FFH | ||
RWW/RWr00 to FFH | ||||||
: High | ||||||
|
|
|
| Monitor Speed |
(Use the default value for settings other than the following.)
Station No. | : 0 (fixed) |
Mode | : Online (normal) |
Network type | : CC IE Field (Master station) |
Network No. | : 1 |
Total stations | : 1 |
Network Configuration Settings : RX/RY00H to FFH
RWW/RWr00H to FFH
■ [Network parameter] of GX Works2
*1 The
The start I/O No. of the
POINT
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of the
Parameter settings (Connection to MELSEC- Q, QS series) of System configuration (Network Type: CC IE Field)
(1)Network parameter] of GX Works2
Use GX Works2 of Version 1.31H or later.
(a)Network parameter
|
|
|
| Setting |
Item |
|
| Set value | necessity at |
|
| GOT | ||
|
|
|
| |
|
|
|
| connection |
Network type |
|
| CC IE Field |
|
| (Master station) (fixed) |
| ||
|
|
| ||
|
|
|
|
|
Starting I/O No.*1 |
|
| 0000H |
|
Network No.*2 |
|
| 1 |
|
Total stations |
|
| 1 |
|
|
|
|
|
|
Station No. |
|
| 0 (fixed) |
|
|
|
|
|
|
Mode*3 |
|
| Online |
|
| (Normal mode) |
| ||
|
|
| ||
|
|
|
|
|
Network Configuration |
|
| Refer to (b) |
|
Settings |
|
|
| |
|
|
|
| |
|
|
|
|
|
Refresh parameters |
|
|
|
|
|
|
|
|
|
Interrupt settings |
| (Use default value) |
| |
|
|
| ||
Interlink transmission |
|
|
|
|
parameters |
|
|
|
|
|
|
|
|
|
Routing parameters |
|
| Refer to (c) |
|
|
|
|
|
|
| : Necessary | : As necessary : Not necessary |
*1 When using Q170MCPU, set it according to the system configuration.
*2 Specify the same network No. as that of the GOT.
*3 Set the same mode setting as that of the GOT.