12.4 PLC Side Setting

This section describes the settings of the GOT and CC- Link IE controller network module in the following case of system configuration.

POINT

CC-Link IE Field Network Module

For details of the CC-Link IE Field Network module, refer to the following manual.

CC-Link IE Field Network Master/Local Module User's Manual

System configuration (Network Type: CC IE Field)

■ GT Designer3 [Communication setting] of System configuration1 (Network Type: CC IE Field)

<GOT>

(Use the default value for settings other

 

 

 

 

than the following.)

 

 

 

 

 

Network type

: CC IE Field

 

 

 

 

Network No.

: 1

 

 

 

 

Station No.

: 1

 

 

 

 

Mode Setting

: Online

 

 

 

 

Network Configuration Settings : RX/RY00 to FFH

CC-Link IE Field Network

RWW/RWr00 to FFH

: High

 

 

 

 

Monitor Speed

<CC-Link IE Field Network module> *1

(Use the default value for settings other than the following.)

Station No.

: 0 (fixed)

Mode

: Online (normal)

Network type

: CC IE Field (Master station)

Network No.

: 1

Total stations

: 1

Network Configuration Settings : RX/RY00H to FFH

RWW/RWr00H to FFH

■ [Network parameter] of GX Works2

*1 The CC-Link IE Field Network module is mounted on slot 0 of the base unit.

The start I/O No. of the CC-Link IE Field Network module is set at [0].

POINT

When connecting to Q170MCPU

When connected to Q170MCPU, the start I/O No. of the CC-Link IE Field Network module is set to "70".

Parameter settings (Connection to MELSEC- Q, QS series) of System configuration (Network Type: CC IE Field)

(1)Network parameter] of GX Works2

Use GX Works2 of Version 1.31H or later.

(a)Network parameter

 

 

 

 

Setting

Item

 

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

connection

Network type

 

 

CC IE Field

 

 

(Master station) (fixed)

 

 

 

 

 

 

 

 

 

Starting I/O No.*1

 

 

0000H

 

Network No.*2

 

 

1

 

Total stations

 

 

1

 

 

 

 

 

 

Station No.

 

 

0 (fixed)

 

 

 

 

 

 

Mode*3

 

 

Online

 

 

(Normal mode)

 

 

 

 

 

 

 

 

 

Network Configuration

 

 

Refer to (b)

 

Settings

 

 

 

 

 

 

 

 

 

 

 

 

Refresh parameters

 

 

 

 

 

 

 

 

 

Interrupt settings

 

(Use default value)

 

 

 

 

Interlink transmission

 

 

 

 

parameters

 

 

 

 

 

 

 

 

 

Routing parameters

 

 

Refer to (c)

 

 

 

 

 

 

 

: Necessary

: As necessary : Not necessary

*1 When using Q170MCPU, set it according to the system configuration.

*2 Specify the same network No. as that of the GOT.

*3 Set the same mode setting as that of the GOT.

12 - 10

12. CC-Link IE FIELD NETWORK CONNECTION

 

12.4 PLC Side Setting