Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
GOT connection destination | Parameters corresponding to inverter |
PU connector | Pr.79, Pr.117 to Pr.124, Pr.342 |
|
|
Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342 | |
|
|
(2)Communication settings of inverter
Set the following parameters using the PU (parameter unit). Set Pr.160 (Extended function display selection) to 1 [All parameters can be accessed for reading and writing.] before making the parameter settings.
Do not change these parameters, even though they can be monitored from the GOT. If they are changed, communication with the GOT is disabled.
Setting item*1 | Parameter No. | Set value |
|
| Contents of setting | |||
PU connector |
|
|
| |||||
|
|
|
|
|
|
| ||
Communication station number | Pr.117 |
| Pr.331 | 0 to 31 |
|
| ||
|
|
| ||||||
|
|
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Communication speed*2 | Pr.118 |
| Pr.332 | 192*4 |
|
|
| 19200bps |
Stop bit length/data length | Pr.119 |
| Pr.333 | 10 |
|
|
| Data length: 7bit |
Stop bit length*2 |
|
|
|
| Stop bit length: 1bit | |||
|
|
|
|
|
|
| ||
Parity check presence/absence*2 | Pr.120 |
| Pr.334 | 1 |
|
|
| Odd |
Number of communication retries | Pr.121 |
| Pr.335 | 9999 |
|
| The inverter will not come to an | |
|
|
|
| alarm stop. | ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Communication check time interval | Pr.122 |
| Pr.336 | 9999 |
|
|
| Communication check |
|
|
|
| suspension | ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Wait time setting | Pr.123 |
| Pr.337 | 0 |
|
|
| 0ms |
|
|
|
|
|
|
|
|
|
CRLF presence/ absence selection | Pr.124 |
| Pr.341 | 1*3 |
|
|
| With CR, without LF |
Protocol selection*5 | ― |
| ― | ― |
|
| ― | |
|
|
|
| PU |
| 1 |
| PU operation mode |
|
|
|
| connector |
|
| ||
Operation mode selection | Pr.79 |
|
|
|
|
| ||
|
|
|
|
|
| |||
|
| 0*3 |
| External operation mode at | ||||
|
|
|
|
|
| |||
|
|
|
|
|
| power on | ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
Link start mode selection*6 | ― |
| Pr.340 | 1 |
|
|
| Computer link operation |
E2PROM write selection | Pr.342 |
| 0*3 |
|
|
| Written to RAM and EEPROM |
*1 Setting items are parameter names described in the manual of
*2 Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3 Inverter default values (No need to change)
*4 Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*5 There is no Protocol selection setting on the inverter side.
*6 The setting is required on the inverter side when
9
TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)
10
MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
11
12
13
14
15
CONNECTION
INVERTER
16
CONNECTION
SERVO AMPLIFIER
15. INVERTER CONNECTION | 15 - 35 |
15.5 FREQROL Series Inverter Side Settings