13.4.3Connecting to CC-Link module (Q Series) with Ver.1/Ver.2 compatibles mixed

This section describes the setting of the GOT and CC-Link module (Q Series) with Ver.1/Ver.2 compatibles mixed in the following system configuration.

POINT

CC-Link module (Q Series)

For details of the CC-Link module (Q Series), refer to the following manual.

Switch setting of CC-Link module (Q Series)

Set the station number setting switch, transmission speed / mode setting switch.

QJ61BT11N

QJ61BT11N

RUN

L RUN

MST

S MST

SD

RD

ERR.

L ERR.

STATION

NO.

X10

5

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

X1

5

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC-Link System Master/Local Module User's Manual QJ61BT11N

System configuration

[Controller Setting] of GT Designer3

Setting of the CC-Link communication unit

<GOT (Ver.1 compatible)>

(Use default value for settings other than the following.)

Station type

: Intelligent device

 

station

Station No.

: Station No. 1

Number of stations

: Exclusive station 1

occupied

 

Transmission speed

: 156kbps

MODE

NC

NC

DA

SLD

DB

(FG)

DG

C

8

0

 

4

1

2

3

4

5

6

7

(2)

 

 

<GOT (Ver.2 compatible)>

 

 

(Use default value for settings other

 

 

than the following.)

 

 

 

Station type

: Intelligent device

 

 

 

station

 

 

Station No.

: Station No. 2

 

 

Expanded cyclic setting

: Single

 

 

Number of stations

: Exclusive station 1

 

 

occupied

 

 

 

<CC-Link module> *1

 

Transmission speed

: 156kbps

(Use default value for settings other than the following.)

 

Type

:

Master station

 

Station No.

:

Station No. 0

 

Mode

: Remote net (Ver.2 mode)

 

All connect count

:

2

 

Transmission speed

:

156kbps

 

Switch setting of CC-Link module (Q Series)

[Network parameter] of GX Developer

*1 The CC-Link module is mounted on the base unit slot 0. The Start I/O No. of the CC-Link module is set to "0"

POINT

When connecting to Q170MCPU

When connected to Q170MCPU, the start I/O No. of the CC-Link module is set to "70".

(1) Station number setting switch

Station number

Description

Set value

Setting necessity

setting switch

at GOT connection

 

 

 

 

 

 

Station number

setting0 (fixed) (master station)

 

: Necessary

: As necessary : Not necessary

(2) Transmission rate/mode setting switch

 

 

 

 

Transmission

 

 

Setting necessity

rate/mode setting

Description

Set value

at GOT connection

switch

 

 

 

 

 

 

 

 

 

Transmission rate/

mode setting 0 (Online:

156kbps)*1

: Necessary : As necessary : Not necessary *1 Specify the same transmission speed as that of the GOT.

POINT

When the switch setting has been changed

Turn the PLC CPU OFF then ON again, or reset the

PLC CPU.

13 - 20

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

 

13.4 PLC Side Setting