The following shows the applicable combinations of connection types, the number of channels, and restricted functions.

 

 

 

 

: Allowed : Restricted

 

 

 

 

 

 

 

GOT to be used

Functions that are restricted by the connection type*1

 

 

GT1695

FA transparent function

 

 

GT1685

 

 

Item

Allowable combination of connection types

GT1675

 

 

GT1672

 

 

 

 

RS-232

USB

 

 

GT1665

 

 

 

 

 

 

GT1662

 

 

 

 

GT1655

 

 

(a)

• Bus/network connection: 1 channel

Max. 4 channels

*2

 

• Serial connection: 1 to 3 channels

 

 

 

 

 

 

 

 

 

 

(b)

• Bus/network connection: 1 channel

Max. 4 channels

*2

 

• Ethernet connection: 1 to 3 channels

 

 

 

 

 

 

 

 

 

 

(c)

• Ethernet connection: 1 to 3 channels

Max. 4 channels

*2

 

• Serial connection: 1 to 3 channels

 

 

 

 

 

 

 

 

 

 

 

• Bus/network connection: 1 channel

 

 

 

(d)

• Ethernet connection: 1 to 2 channels

Max. 4 channels

*2

 

 

• Serial connection: 1 to 2 channels

 

 

 

 

 

 

 

 

(e)

• Serial connection: 4 channels

Max. 4 channels

*2

 

 

 

 

 

 

(f)

• Ethernet connection:: 4 channels

Max. 4 channels

*2

 

 

 

 

 

 

*1

When the functions below are used, the connectable number of channels may be restricted depending on the combination of the

 

 

functions to be used.

 

 

 

 

Fingerprint authentication

Barcode function

RFID function

 

 

Remote personal computer operation

Video display function

Multimedia function

 

 

Operation panel function

External I/O function

RGB display function

 

 

Report function

Hard copy function(for printer output)

Sound output function

 

 

Functions with the CF card unit or CF card extension unit

 

 

 

The video display function, multimedia function and RGB display function cannot be used together.

 

 

The CF card unit and the CF card extension unit cannot be used at the same time.

 

 

 

For details, refer to the following.

 

 

 

 

21.3.4 Determining the GOT side interface (Interface selection)

 

 

 

 

*2

 

For the FA transparent function via the RS-232 connection, the RS-232 interface built in the GOT is available only.

 

 

When the RS-232 interface built in the GOT is already used, the FA transparent function is not available.

17

ROBOT CONTROLLER CONNECTION

18

CNC CONNECTION

19

CONNECTION

GOT MULTI-DROP

20

MULTIPLE-GT14, GT12, GT11, GT10 CONNECTION FUNCTION

21

FUNCTION

MULTI-CHANNEL

22

FUNCTION

FA TRANSPARENT

21. MULTI-CHANNEL FUNCTION

21 - 15