Select [Common] menu.
The settings of connecting equipment confirmed in [I/F Communication Setting]. For details, refer to the following.
1.1.2 I/F communication setting
can
4. The detailed setting is displayed after Manufacturer, Controller Type, I/F, and Driver are set.
Make the settings according to the usage environment.
10.3.2 Communication detail settings Click the [OK] button when settings are completed.
POINT
The Controller Setting window is displayed. Select the channel to be used from the list menu.
[Controller Setting] from the
1.
2.
3. Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller Type to be connected.
• I/F: Interface to be used
• Driver:
When using the MELSECNET/H communication unit
MELSECNET/H
When using the MELSECNET/10 communication unit
MELSECNET/10
10.3 GOT Side Settings
10.3.1 Setting communication interface (Communication settings)
Set the channel of the connected equipment.
2.
3.
4.
Click!
10.3.2Communication detail settings

Make the settings according to the usage environment.

(1) MELSECNET/H

Item

Description

Range

 

 

• MNET/H mode

Network Type

Set the network type.

• MNET/10 mode

(Default: MNET/H mode)

• MNET/H Extended

 

 

mode*1

Network No.

Set the network No.

1 to 239

(Default: 1)

 

 

 

 

 

Station No.

Set the station No. of the GOT.

1 to 64

(Default: 1)

 

 

 

 

 

 

 

• Online

 

 

(Auto Reconnect)

 

 

• Offline

 

Set the operation mode of the

• Test between

 

slave station*2

Mode Setting

GOT.

(Default:

Self-loopback test*2

 

Online (auto. reconnection))

• Internal self-

 

 

loopback

 

 

test*2

 

 

• H/W test*2

 

Set the number of retries to be

 

 

performed when a communication

 

 

timeout occurs.

 

Retry

When no response is received

0 to 5times

 

after retries, a communication

 

 

times out.

 

 

(Default: 3times)

 

 

 

 

 

Set the time period for a

 

Timeout Time

communication to time out.

3 to 90sec

 

(Default: 3sec)

 

 

 

 

 

Set the delay time for reducing the

 

Delay Time

load of the network/destination

0 to 300ms

PLC.

 

 

 

(Default: 0ms)

 

 

 

 

be

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

10 - 9

10.3 GOT Side Settings