13.3.3Switch setting (Only when MODEL GT15-75J61BT13-Z CC-Link communication unit is used)

POINT

Switch setting of the communication unit

When using the MODEL GT15-J61BT13 CC-Link communication unit, the switch setting is not needed.

For details of each setting switch and LED, refer to the following manual.

GT15 CC-Link communication unit User's Manual

 

 

 

 

GT15-75J61BT13-Z

Left side

Front side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) Transmission baudrate setting switch

Transmission

 

 

baudrate

Description

Set value

setting switch

 

 

 

 

0: 156kbps

 

Specify the transmission speed.

1: 625kbps

 

2: 2.5Mbps

 

(Default: 0)

 

3: 5Mbps

 

 

 

 

4: 10Mbps

 

 

 

(4) Condition setting switches

Condition

Setting

 

 

setting

Description

Set value

switch

switches

 

 

 

 

 

 

 

 

 

Specify input data status of

OFF: Cleared

 

 

 

SW1

the data link error station.

 

 

 

ON: Held

 

 

 

 

(Default: OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specify the number of stations

OFF: 1 station

 

 

 

 

 

 

 

SW2

occupied.

 

 

 

ON: 4 stations

 

 

 

 

(Default: OFF)

 

 

 

 

 

 

 

 

 

 

 

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

(1)

 

 

3456

 

 

2

 

 

 

7

 

 

 

EDCBA9

 

 

 

1

 

 

 

 

 

 

 

0F

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

1

2

34

 

 

 

0

 

 

 

5

(2)

 

 

9

 

7

6

 

 

 

 

8

 

 

 

1

2

34

 

 

 

0

 

 

 

5

 

 

 

9

 

 

6

(3)

 

 

 

 

8

7

 

 

 

 

 

2

34

 

 

98

7

6

 

 

 

1

 

 

 

 

(4)

 

 

0

 

 

 

5

 

 

2 1ON

 

 

 

 

 

RUN

L RUN

SD

RD

MODE L ERR.

10

STATION NO.

1

BAUDRATE

 

 

 

 

 

 

1

 

 

3

 

 

5

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW

 

ON

 

OFF

 

 

DA

 

DG

NC

 

NC

 

 

 

 

 

 

 

1

 

HOLD

 

CLEAR

 

 

 

2

 

 

4

 

6

 

 

 

8

 

2

 

4

 

1

 

 

 

DB

 

SLD

(FG1)

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POINT

(1)Switch setting example

For the switch setting example, refer to the following.

13.4 PLC Side Setting

12

CC-Link IE FIELD NETWORK CONNECTION

(1) Mode setting switch

Mode setting

Description

Set value

switch

 

 

 

Select the online mode.

0 (fixed)

 

(Default: 0)

 

 

 

 

 

(2) Station number setting switch

Station

numberDescriptionSet value setting

switch

Specify the station No. of the CC-

Link communication unit.1 to 64 (Default: 01)

(2)When the switch setting is changed

When changing the switch setting after mounting the MODEL GT15-75J61BT13-Z CC-Link communication unit on the GOT, reset the GOT.

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

13 - 11

13.3 GOT Side Settings