(3)Calculation example
(a)When connecting the
Current supply capacity of GOT (A) | Total consumed current (A) |
2.2 | 0.77+0.33+0.33+0.33+0.224+0.12=2.104 |
Since the calculated value is within the capacity of the GOT, they can be connected to the GOT.
(b)When connecting the
Current supply capacity of GOT (A) | Total consumed current (A) |
1.74 | 0.77+0.33+0.33+0.224+0.12=1.774 |
Since the calculated value exceeds the capacity of the GOT, such configuration is not allowed.