*1 Transmission speed settings

The following lists the transmission speed settings of the CC- Link communication.

Set value

Description

0

Online: 156kbps

 

 

1

Online: 625kbps

 

 

2

Online: 2.5Mbps

 

 

3

Online: 5Mbps

 

 

4

Online: 10Mbps

 

 

A

Hardware test: 156kbps

 

 

B

Hardware test: 625kbps

 

 

C

Hardware test: 2.5Mbps

 

 

D

Hardware test: 5Mbps

 

 

E

Hardware test: 10Mbps

 

 

For details of the hardware test, refer to the following manual.

CC-Link System Master/Local Module User's Manual for CC-Link module to be used

(2) CC-Link(ID)

Item

Description

Range

 

Set the number of retries to be

 

 

performed when a communication

 

Retry

timeout occurs.

0 to 5times

When no response is received after

 

 

 

retries, a communication times out.

 

 

(Default: 3times)

 

 

 

 

 

Set the time period for a communication

 

Timeout Time

to time out.

3 to 90sec

 

(Default: 3sec)

 

 

 

 

POINT

(1)Communication interface setting by Utility The communication interface setting can be changed on the Utility's [Communication Settings] after writing [Communication Settings] of project data.

For details on the Utility, refer to the following manual.

GT User's Manual

(2)Precedence in communication settings

When settings are made by GT Designer3 or the Utility, the latest setting is effective.

13 - 10

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

 

13.3 GOT Side Settings