*1 Transmission speed settings
The following lists the transmission speed settings of the CC- Link communication.
Set value | Description |
0 | Online: 156kbps |
|
|
1 | Online: 625kbps |
|
|
2 | Online: 2.5Mbps |
|
|
3 | Online: 5Mbps |
|
|
4 | Online: 10Mbps |
|
|
A | Hardware test: 156kbps |
|
|
B | Hardware test: 625kbps |
|
|
C | Hardware test: 2.5Mbps |
|
|
D | Hardware test: 5Mbps |
|
|
E | Hardware test: 10Mbps |
|
|
For details of the hardware test, refer to the following manual.
(2)
Item | Description | Range | |
| Set the number of retries to be |
| |
| performed when a communication |
| |
Retry | timeout occurs. | 0 to 5times | |
When no response is received after | |||
|
| ||
| retries, a communication times out. |
| |
| (Default: 3times) |
| |
|
|
| |
| Set the time period for a communication |
| |
Timeout Time | to time out. | 3 to 90sec | |
| (Default: 3sec) |
| |
|
|
|
POINT
(1)Communication interface setting by Utility The communication interface setting can be changed on the Utility's [Communication Settings] after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GT User's Manual
(2)Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
13 - 10 | 13. |
| 13.3 GOT Side Settings |