[Network parameter] of GX Developer | (2) Station information setting |
(1) Network parameter |
|
|
| Setting | |
Item | Set value | necessity at | |
GOT | |||
|
| ||
|
| connection | |
No. of boards in module | 1 |
| |
|
|
| |
Start I/O No.*1 | 0000H |
| |
Operation setting | (Use default value) |
| |
|
|
| |
Type | Master station (fixed) |
| |
|
|
| |
Mode | Remote net |
| |
(Ver.2 mode) |
| ||
|
| ||
|
|
| |
All connect count | 1 |
| |
|
|
| |
Remote input (RX) | X400 |
| |
|
|
| |
Remote output (RY) | Y400 |
| |
|
|
| |
Remote register (RWr) | D300 |
| |
|
|
| |
Remote register (RWw) | D200 |
| |
|
|
| |
Special relay (SB) | SB0 |
| |
|
|
| |
Special register (SW) | SW0 |
| |
|
|
| |
Retry count |
|
| |
|
|
| |
Automatic reconnection |
|
| |
station count |
|
| |
|
|
| |
Stand by master station No. | (Use default value) |
| |
|
| ||
PLC down select |
|
| |
|
|
| |
Scan mode setting |
|
| |
|
|
| |
Delay information setting |
|
| |
|
|
| |
Station information setting | Refer to (2) |
| |
|
|
| |
Remote device station initial |
|
| |
setting | (Use default value) |
| |
|
| ||
Interrupt setting |
|
| |
|
|
|
: Necessary
: As necessary
: Not necessary
*1 Set the Start I/O No. of the
|
|
| Setting |
Item*1 |
| Set value | necessity at |
| GOT | ||
|
|
| |
|
|
| connection |
Station type | Ver.2 intelligent device |
| |
| station (fixed) |
| |
|
|
| |
|
|
|
|
Expanded cyclic setting*2 |
| Single |
|
Exclusive station count*2 | Exclusive station 1 |
| |
Remote station points | 32 points (fixed) |
| |
|
|
|
|
Reserve/invalid station select |
| No setting |
|
|
|
| |
Intelligent buffer select (word) | (Use default value) |
| |
|
|
|
|
: Necessary | : As necessary : Not necessary |
*1 When the [Mode] of the
*2 Set the same setting as that of the GOT.
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU, operate the PLC CPU either turning OFF and then ON or resetting.
[Controller Setting] of GT Designer3
Item | Set value |
Station No. | 1: Station No.1 |
|
|
Transmission Rate | 0: Online 156kbps |
|
|
Mode | Ver.2: Remote net (Ver.2 mode) |
|
|
Expanded Cyclic | Single |
|
|
Number of stations occupied | 1 Station |
|
|
Input for Error Station | 0: Clear |
|
|
Retry | 3times (Use default value) |
|
|
Timeout Time | 3sec (Use default value) |
|
|
Delay Time | 0ms (Use default value) |
|
|
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT Designer3, refer to the following.
13.3.1 Setting communication interface (Communication settings)
13 - 26 | 13. |
| 13.4 PLC Side Setting |