[Network parameter] of GX Developer

(2) Station information setting

(1) Network parameter

 

 

 

Setting

Item

Set value

necessity at

GOT

 

 

 

 

connection

No. of boards in module

1

 

 

 

 

Start I/O No.*1

0000H

 

Operation setting

(Use default value)

 

 

 

 

Type

Master station (fixed)

 

 

 

 

Mode

Remote net

 

(Ver.2 mode)

 

 

 

 

 

 

All connect count

1

 

 

 

 

Remote input (RX)

X400

 

 

 

 

Remote output (RY)

Y400

 

 

 

 

Remote register (RWr)

D300

 

 

 

 

Remote register (RWw)

D200

 

 

 

 

Special relay (SB)

SB0

 

 

 

 

Special register (SW)

SW0

 

 

 

 

Retry count

 

 

 

 

 

Automatic reconnection

 

 

station count

 

 

 

 

 

Stand by master station No.

(Use default value)

 

 

 

PLC down select

 

 

 

 

 

Scan mode setting

 

 

 

 

 

Delay information setting

 

 

 

 

 

Station information setting

Refer to (2)

 

 

 

 

Remote device station initial

 

 

setting

(Use default value)

 

 

 

Interrupt setting

 

 

 

 

 

: Necessary : As necessary : Not necessary

*1 Set the Start I/O No. of the CC-Link module according to the system configuration.

 

 

 

Setting

Item*1

 

Set value

necessity at

 

GOT

 

 

 

 

 

 

connection

Station type

Ver.2 intelligent device

 

 

station (fixed)

 

 

 

 

 

 

 

 

Expanded cyclic setting*2

 

Single

 

Exclusive station count*2

Exclusive station 1

 

Remote station points

32 points (fixed)

 

 

 

 

 

Reserve/invalid station select

 

No setting

 

 

 

 

Intelligent buffer select (word)

(Use default value)

 

 

 

 

 

: Necessary

: As necessary : Not necessary

*1 When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 2 mode)], [Remote station points] can be set. [Remote station points] is a setting for the remote I/O station. The default value (32 points) must be used on the GOT.

*2 Set the same setting as that of the GOT.

POINT

When changing the network parameter

After writing the network parameter to the PLC CPU, operate the PLC CPU either turning OFF and then ON or resetting.

[Controller Setting] of GT Designer3

Item

Set value

Station No.

1: Station No.1

 

 

Transmission Rate

0: Online 156kbps

 

 

Mode

Ver.2: Remote net (Ver.2 mode)

 

 

Expanded Cyclic

Single

 

 

Number of stations occupied

1 Station

 

 

Input for Error Station

0: Clear

 

 

Retry

3times (Use default value)

 

 

Timeout Time

3sec (Use default value)

 

 

Delay Time

0ms (Use default value)

 

 

POINT

[Controller Setting] of GT Designer3

For the setting method of [Controller Setting] of GT Designer3, refer to the following.

13.3.1 Setting communication interface (Communication settings)

13 - 26

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

 

13.4 PLC Side Setting