Output stop(MRS) | Second function selection(RT) | High speed operation command(RH) | Middle speed operation command(RM) | Low speed operation command(RL) | Reverse rotation command(STR) | Forward rotation command(STF) | Current input selection(AU) |
WS7: | WS6: | WS5: | WS4: | WS3: | WS2: | WS1: | WS0: |
Device SP122 0 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0
b15 | b7 | b0 |
Write [1] to each bit corresponding to Forward rotation command (WS1) and Low speed operation command (WS3) of device SP122. The value will be 000AH in this example. When writing the value to device SP122 actually, convert 000AH to decimal number and write the value [10].
When using a WS device, [Alternate] of a bit switch cannot be used.
Use [Set], [Reset], and [Momentary] of a bit switch.
The following shows correspondences between virtual inverter devices used in the GOT and data of the inverter.
(1)Inverter status monitor
An example with
User's Manual of the used inverter (communication function (setting item and set data))
Device name | Description*1 |
RS0 | Inverter running (RUN) |
|
|
RS1 | Forward rotation (STF) |
|
|
RS2 | Reverse rotation (STR) |
|
|
RS3 | Up to frequency (SU) |
|
|
RS4 | Overload (OL) |
|
|
RS5 | Instantaneous power failure (IPF) |
|
|
RS6 | Frequency detection (FU) |
|
|
RS7 | Fault (ABC1) |
|
|
RS8 | ABC2 |
|
|
RS9 | - |
|
|
RS10 | - |
|
|
RS11 | - |
|
|
RS12 | - |
|
|
RS13 | - |
|
|
RS14 | - |
|
|
RS15 | Fault occurrence |
|
|
*1 The description (function of input terminal) may be changed by the parameter of the inverter side. Check the function of the inverter used.
Inverter User's Manual (Application) Communication operation and setting
(2)Run command
An example with
User's Manual of the used inverter (Communication function (Setting item and set data))
Device name | Description*1 | |
WS0 | Current input selection (AU) | |
|
| |
WS1 | Forward rotation command (STF) | |
|
| |
WS2 | Reverse rotation command (STR) | |
|
| |
WS3 | Low speed operation command (RL) | |
|
| |
WS4 | Middle speed operation command (RM) | |
|
| |
WS5 | High speed operation command (RH) | |
|
| |
WS6 | Second function selection (RT) | |
|
| |
WS7 | Output stop (MRS) | |
|
| |
WS8 | Jog operation (JOG) | |
|
| |
WS9 | Selection of automatic restart after instantaneous | |
power failure (CS) | ||
| ||
|
| |
WS10 | Start | |
|
| |
WS11 | Reset (RES) | |
|
| |
WS12 | - | |
|
| |
WS13 | - | |
|
| |
WS14 | - | |
|
| |
WS15 | - | |
|
|
*1 The data (function of input terminal) may be changed by the parameter of the inverter side. Check the function of the inverter used.
Inverter User's Manual (Application) Communication operation and setting
(3) Alarm definition
Device name*1 | Description |
A0 | Second alarm in past |
|
|
A1 | Latest alarm |
|
|
A2 | Fourth alarm in past |
|
|
A3 | Third alarm in past |
|
|
A4 | Sixth alarm in past |
|
|
A5 | Fifth alarm in past |
|
|
A6 | Eighth alarm in past |
|
|
A7 | Seventh alarm in past |
|
|
*1 Only reading is possible for A0 to A7.
These devices cannot be used for a write object (numerical input etc.).
(4)Parameter
The numbers of virtual devices for inverter (parameter (Pr)), used by GOT, correspond to the inverter parameter numbers.
For the inverter parameters, refer to the following.
Manual of the inverter being used
9
TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)
10
MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
11
12
13
14
15
CONNECTION
INVERTER
16
CONNECTION
SERVO AMPLIFIER
15. INVERTER CONNECTION | 15 - 45 |