(2)[Parameter Setting] of CC-Link utility

(a)Network parameter

 

 

 

Setting

 

Item

Set value

necessity

 

at GOT

 

 

 

 

 

 

connection

Number of modules

1

 

 

 

 

Target module

1

 

 

 

 

Start I/O No.

0000H

 

 

 

 

Channel No.

(Use default value)

 

 

 

 

 

 

type

Master station(fixed)

 

 

 

 

 

 

Mode*1

Remote net

 

 

(Ver.1 mode)

 

 

 

 

 

 

 

 

 

Expanded cyclic

Single(fixed)

 

 

station

 

 

 

 

 

 

 

 

Operation

Occupied number

Exclusive station 1

 

setting

 

(fixed)

 

 

Error event : input data

Clear

 

 

status

 

 

 

 

 

 

 

 

 

CPU stop: data link

Refresh

 

 

status

 

 

 

 

 

 

 

 

 

Other settings

(Use default value)

 

 

 

 

 

 

All connect count

1

 

 

 

 

 

 

Station type

Ver.1 Intelligent device

 

 

station(fixed)

 

 

 

 

 

 

 

 

 

Expanded cyclic

Single

 

Station

station

 

 

 

 

 

 

information

Occupied number*2

Exclusive station 1

 

settings

 

 

 

Remote station points

32 points

 

 

 

 

 

 

 

 

Reserve/invalid station

No setting

 

 

select

 

 

 

 

 

 

 

 

 

Intelligent buffer select

(Use default value)

 

 

(word)

 

 

 

 

 

 

 

 

: Necessary : As necessary : Not necessary

*1 If the CC-Link module [Mode] is [Remote net -Ver.1 mode], [Remote station points] cannot be set.

*2 Set the same setting as that of the GOT.

POINT

When changing the network parameter

After writing the network parameter to the C Controller module, either turn the C Controller module OFF and then ON or reset it.

14.5.6[Controller Setting] of GT Designer3

Item

Set value

 

9600bps

 

19200bps

Transmission Speed

38400bps

 

57600bps

 

115200bps

 

 

Retry Count

0 to 5times

 

 

Timeout Time

3 to 30sec

 

 

Delay Time

0 to 300ms

 

 

POINT

[Controller Setting] of GT Designer3

For [Controller Setting], of GT Designer3, refer to the following.

14.4.1 Setting communication interface (Communication settings)

14 - 16

14. CC-Link CONNECTION (Via G4)

 

14.5 PLC Side Settings