(4) CC-Link Ver.2 (ID)

(5) CC-Link(ID)

Item

Description

Range

Station No.

Set the station No. of the GOT.

1 to 64

(Default: 1)

 

 

 

 

 

Transmission

Set the transmission speed and

 

the mode of the GOT.

0 to E

Rate*1

(Default: 0)

 

 

 

 

 

 

 

Set the mode of CC-Link.

Ver.1/Ver.2/

Mode

Additional/

(Default: Ver.1)

 

Offline

 

 

 

 

 

 

 

Single/

Expanded

Set the cyclic point expansion.

Double/

Cyclic

(Default: Single)

Quadruple/

 

 

Octuple

 

 

 

Occupied

Set the number of stations

 

occupied by the GOT.

1 Station/4 Stations

Station

(Default: 1 Station)

 

 

 

 

 

 

Input for Error

Set Clear/Hold at an error

 

occurrence.

Clear/Hold

Station

(Default: Clear)

 

 

 

 

 

 

 

Set the number of retries to be

 

 

performed when a communication

 

 

timeout occurs.

 

Retry

When no response is received

0 to 5times

 

after retries, a communication

 

 

times out.

 

 

(Default: 3times)

 

 

 

 

 

Set the time period for a

 

Timeout Time

communication to time out.

3 to 90sec

 

(Default: 3sec)

 

 

 

 

 

Set the delay time for reducing the

 

Delay Time

load of the network/destination

0 to 300ms

PLC.

 

 

 

(Default: 0ms)

 

 

 

 

*1 Transmission speed settings

The following lists the transmission speed settings of the CC- Link communication.

Set value

Description

0

Online: 156kbps

 

 

1

Online: 625kbps

 

 

2

Online: 2.5Mbps

 

 

3

Online: 5Mbps

 

 

4

Online: 10Mbps

 

 

A

Hardware test: 156kbps

 

 

B

Hardware test: 625kbps

 

 

C

Hardware test: 2.5Mbps

 

 

D

Hardware test: 5Mbps

 

 

E

Hardware test: 10Mbps

 

 

For details of the hardware test, refer to the following manual.

CC-Link System Master/Local Module User's Manual for CC-Link module to be used

Item

Description

Range

 

Set the number of retries to be

 

 

performed when a communication

 

Retry

timeout occurs.

0 to 5times

When receiving no response after

 

 

 

retries, the communication times out.

 

 

(Default: 3times)

 

 

 

 

 

Set the time period for a communication

 

Timeout Time

to time out.

3 to 90sec

 

(Default: 3sec)

 

 

 

 

18 - 10

18. CNC CONNECTION

 