Parameter settings (Connection to Universal model QCPU) of System configuration2 (Network Type: Extended mode)

(1)[Network parameter] of GX Works2

(a)Network parameter

 

 

 

Setting necessity

Item

 

Set value

at GOT

 

 

 

connection

Network Type

 

CC IE Control Ext. Mode

 

 

(Control station) (fixed)

 

 

 

 

 

 

 

 

Start I/O No.*1

 

0000H

 

Network No.*2

1

 

Total Stations

2

 

 

 

 

 

Group No.

 

0 (Fixed)

 

 

 

 

 

Station No.

1

 

 

 

 

 

Mode*3

 

Online

 

Network Range

Same as the following setting

 

 

[Network parameter]

 

Assignment

 

 

 

of GX Developer

 

 

 

 

 

 

 

 

Refresh Parameters

 

 

 

 

 

 

 

Interrupt Setting

 

(Use default value)

 

 

 

 

Interlink transmission

 

 

 

parameters

 

 

 

 

 

 

 

 

Same as the following setting

 

Routing parameters

 

[Network parameter]

 

 

 

 

 

of GX Developer

 

 

 

 

 

 

: Necessary : As necessary

: Not necessary

(2) [Controller Setting] of GT Designer3

Item

Set value

Network type

CC IE Control extended mode

 

 

Network No.

1: Network No.1

 

 

Station No.

2: Station No.2

 

 

Mode

Online (auto. reconnection)

 

 

Retry

3times (Use default value)

 

 

Timeout Time

3sec (Use default value)

 

 

Delay Time

1ms (Use default value)

 

 

Refresh Interval

High (Use default value)

 

 

Monitor Speed

High (Use default value)

 

 

POINT

(1)Network type of the GOT side

When the network is in the extended mode, be sure to set the network type of the GOT side to [CC IE Control extended mode].

For [Controller Setting], of GT Designer3, refer to the following.

11.3.1 Setting communication interface (Communication settings)

(2)Network type of the PLC side

Only GX Works2 can set [CC IE Control extended mode (control station)] or [CC IE Control extended mode (ordinary station)]. The CPU which is compatible with the extended mode is Universal model QCPU only.

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

11. CC-Link IE CONTROLLER NETWORK CONNECTION

11 - 15

11.4 PLC Side Setting