[Controller Setting] and [Ethernet] of GT Designer3
POINT
(1)[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT Designer3, refer to the following.
8.3.1 Setting communication interface (Communication settings)
(2)Ethernet setting
When connecting
However, these virtual values must be set on the GOT side. Therefore, set the network No. and station No.
Therefore, set the network No. and station No. Set the network No. that is not existed on the network system and any station No..
(3)Controller setting
Item | Set value (Use default value) | |
GOT NET No. | 1 | |
|
| |
GOT PLC No. | 1 | |
|
| |
GOT IP Address | 192.168.3.1 | |
|
| |
GOT Port No. | 5001 | |
(Communication) | ||
| ||
|
| |
GOT Port No. | 5014 | |
(Ethernet Download) | ||
| ||
|
| |
Default Gateway | 0.0.0.0 | |
|
| |
Subnet Mask | 255.255.255.0 | |
|
| |
Retry | 3times | |
|
| |
Startup Time | 3sec | |
|
| |
Timeout Time | 3sec | |
|
| |
Delay Time | 0ms | |
|
|
(4) Ethernet setting
| Item | Set value | |
| Host | * | |
|
|
| |
| N/W No. | 1*1 | |
Ethernet | PLC No. | 2*2 | |
Type | QnUDE(H), LCPU | ||
setting No.1 | |||
|
| ||
| IP address | 192.168.3.39 | |
|
|
| |
| Port No. | 5006 (fixed) | |
|
|
| |
| Communication | UDP (fixed) | |
|
|
|
*1 Set the same value as that of GOT N/W No.
*2 Set a value different from that of GOT PLC No.
Checking communication state of Connecting to
(1)When using the Command Prompt of Windows®. Execute a Ping command at the Command Prompt of Windows®.
(a)When normal communication C:\>Ping 192.168.3.39
Reply from 192.168.3.2: bytes=32 time <10ms TTL=32
(b)When abnormal communication C:\>Ping 192.168.3.39 Request timed out.
(2)When abnormal communication
At abnormal communication, check the followings and execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of
POINT
Ethernet diagnostics of GX Developer
Ethernet diagnostics of GX Developer is available to a Ping test from the PLC.
For details of Ethernet diagnostics of GX Developer, refer to the following manual.
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
1
PREPARATORYFORPROCEDURESMONITORING 2
RANGESETBE
DEVICE CANTHAT 3
RANGEACCESS MONITORINGFOR 4
MONITORTOREDUNTANTSYSTEM HOW 5
CONNECTIONBUS 6
DIRECTTOCONNECTIONCPU 7
LINKCOMPUTER CONNECTION 8
ETHERNETCONNECTION
8. ETHERNET CONNECTION | 8 - 21 |
8.4 PLC Side Setting |
|