
Item |
|
| Description | |
Extension I/F setting |
| Set the communication unit attached to the extension interface of the GOT. | ||
|
|
|
| |
|
| Set the CH No. according to the intended purpose. | ||
|
| The number of channels differs depending on the GOT to be used. | ||
|
| 0: Not used |
| |
|
| 1 to 4: Used for connecting a controller of channel No. 1 to 4 set in Setting connected equipment (Channel | ||
|
| setting) |
| |
| CH No. | 5 to 7: Used for barcode function, RFID function, remote personal computer operation (serial), report function | ||
| (when using the serial printer) or hard copy function (when using the serial printer) | |||
|
| |||
|
| * : Used for remote personal computer operation (Ethernet), video display function, multimedia function, | ||
|
|
| operation panel function, external I/O function, RGB display function, report function (when using a | |
|
|
| PictBridge compatible printer), hard copy function (when using a PictBridge compatible printer), sound | |
|
|
| output function, functions with the CF card unit or CF card extension unit, Ethernet download, gateway | |
|
|
| function or MES interface function | |
|
|
|
| |
| Driver | Set the driver for the device to be connected. | ||
|
| None | Each driver for connected devices | |
|
|
| ||
|
|
|
| |
| Detail Setting | Make settings for the transmission speed and data length of the communication driver. | ||
|
| Refer to each chapter of the equipment to be connected to the GOT. | ||
|
|
| ||
|
|
|
|
|
POINT
Channel No., drivers, [RS232 Setting]
(1)Channel No.2 to No.4
Use the channel No.2 to No.4 when using the
Mitsubishi Products 21.
(2)Drivers
The displayed items for a driver differ according to the settings [Manufacturer], [Controller Type] and [I/F]. When the driver to be set is not displayed, confirm if [Manufacturer], [Controller Type] and [I/F] are correct.
[Setting the communication] section in each chapter
(3)[RS232 Setting] of GT14
Do not use [RS232 Setting] of GT14 for other than the 5V power feeding to the
For details, refer to the following manual.
GT14 User's Manual 7.11
(1)When using the multiple CPU system
When using the GOT to monitor the multiple CPU system of other stations, select
(2)Precautions for changing model
(a)When devices that cannot be converted are included.
When setting of [Manufacturer] or [Controller Type] is changed, GT Designer3 displays the device that cannot be converted (no corresponding device type, or excessive setting ranges as [??]. In this case, set the device again.
(b)When the changed Manufacturer or Controller Type does not correspond to the network. The network will be set to the host station.
(c)When the Manufacturer or Controller Type is changed to [None]
The GT Designer3 displays the device of the changed channel No. as [??]. In this case, set the device again.
Since the channel No. is retained, the objects can be reused in other channel No. in a batch by using the [Device Bach Edit], [CH No. Batch Edit] or [Device List].
1 - 14 | 1. PREPARATORY PROCEDURES FOR MONITORING |
| 1.1 Setting the Communication Interface |