Confirming the communication state of Ethernet module

(1)When using the Command Prompt of Windows®. Execute a Ping command at the Command Prompt of Windows®.

(a)When normal communication C:\>Ping 192.168.0.19

Reply from 192.168.0.19: bytes=32 time<1ms TTL=64

(b)When abnormal communication C:\>Ping 192.168.0.19 Request timed out.

(2)When abnormal communication

At abnormal communication, check the followings and execute the Ping command again.

• Mounting condition of Ethernet communication unit

• Cable connecting condition

• Confirmation of switch and network parameter setting

• Operation state of PLC CPU (faulty or not)

• IP address of GOT specified by Ping command

POINT

Ethernet diagnostics of GX Developer

Ethernet diagnostics of GX Developer is available to a Ping test from the PLC.

For details of Ethernet diagnostics of GX Developer, refer to the following manual.

User's manual of the Ethernet module

8.4.4Connecting to C Controller module

This section describes the settings of the GOT and C Controller module in the following case of the system configuration.

POINT

C Controller module

For details of C Controller module, refer to the following manual.

C Controller Module User's Manual (Hardware Design, Function Explanation)

System configuration

[Controller Setting] and [Ethernet] of GT

Designer3

<GOT>

 

(The settings other than the

following are set to the default)

Network No.

: 1

PLC No.

: 1

IP address

: 192.168.3.18

Port No.

: 5001

Communication : UDP(fixed)

format

 

<C controller module>

1 (The settings other than the following are set to the default)

Network No.

: 1 (virtual) *1

PLC No.

: 2 (virtual) *1

IP address

: 192.168.3.1

Port No.

: 5006(fixed)

Communication : UDP(fixed) format

<C controller module>

2 (The settings other than the following are set to the default)

Network No.

: 1 (virtual) *1

PLC No.

: 3 (virtual) *1

IP address

: 192.168.3.2

Port No.

: 5006(fixed)

Communication : UDP(fixed) format

Utility setting for C Controller module

*1 These setting items do not exist at the PLC side. However, the virtual values must be set on the GOT side.

[Controller Setting] and [Ethernet] of GT Designer3

1

PREPARATORYFORPROCEDURESMONITORING 2

RANGESETBE

DEVICE CANTHAT 3

RANGEACCESS MONITORINGFOR 4

MONITORTOREDUNTANTSYSTEM HOW 5

CONNECTIONBUS 6

DIRECTTOCONNECTIONCPU 7

LINKCOMPUTER CONNECTION 8

ETHERNETCONNECTION

8. ETHERNET CONNECTION

8 - 27

8.4 PLC Side Setting