HINT
(1)Automatic setting with Pr.999
If Pr.999 is set as the following, the communication settings other than [PU communication station number] and [Communication EEPROM write selection] can be automatically set in a batch to the default communication settings of the GOT side.
Parameter No. | Set value | Description | Operation in parameter setting mode | |
Pr.999*1 | 10 | GOT Initial settings (PU connector) | [AUTO] [GOT] [1]Write | |
|
|
| ||
11 | GOT Initial settings | ― | ||
| ||||
|
|
|
|
*1 When monitoring the value of Pr.999, 9999 is always monitored.
(2)Inverters available for automatic batch setting
Parameters are not automatically set in a batch depending on the SERIAL (production number) symbol of the inverter to be used. For details, contact your local distributor.
15.5.11ConnectingCommunication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating each parameter.
(1) Communication port and corresponding parameters
GOT connection | Parameters corresponding to inverter | |
destination | ||
| ||
PU connector | Pr.79, Pr.117 to Pr.124 | |
|
|
(2)Communication settings of inverter
•Set the following parameters using the PU (parameter unit).
•After setting the parameters for the communication settings, reset the inverter.
•Do not change these parameters, even though they can be monitored from the GOT. If they are changed, communication with the GOT is disabled.
Setting item*1 | Parameter No. | Set value |
| Contents of setting |
Communication station number | Pr.117 | 0 to 31 |
| |
| ||||
|
|
|
|
|
Communication speed*2 | Pr.118 | 192*3 |
| 19200bps |
Stop bit length/data length*2 | Pr.119 | 10 |
| Data length: 7bit |
| Stop bit length: 1bit | |||
|
|
|
| |
|
|
|
|
|
Parity check presence/absence*2 | Pr.120 | 1 |
| Odd |
Number of communication retries | Pr.121 | 9999 | The inverter will not come to an alarm stop. | |
|
|
|
|
|
Communication check time interval | Pr.122 | 9999 |
| Communication check suspension |
|
|
|
|
|
Wait time setting | Pr.123 | 0 |
| 0ms |
|
|
|
|
|
CRLF presence/absence selection | Pr.124 | 1*3 |
| With CR, without LF |
*1 Setting items are parameter names described in the manual of MELIPM series.
*2 Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3 Inverter default values (No need to change)
15 - 42 | 15. INVERTER CONNECTION |
| 15.5 FREQROL Series Inverter Side Settings |