(b) GT15, GT12
Item | Description | Range | |
GOT NET No. | Set the network No. of the GOT. | 1 to 239 | |
(Default: 1) | |||
|
| ||
|
|
| |
GOT PLC No. | Set the station No. of the GOT. | 1 to 64 | |
(Default: 1) | |||
|
| ||
|
|
| |
GOT IP | Set the IP address of the GOT. | 0.0.0.0 to | |
Address | (Default: 192.168.0.18) | 255.255.255.255 | |
|
|
| |
| Set the subnet mask for the sub |
| |
| network.(Only for connection via |
| |
Subnet Mask | router) | 0.0.0.0 to | |
If the sub network is not used, the | 255.255.255.255 | ||
| |||
| default value is set. |
| |
| (Default: 255.255.255.0) |
| |
|
|
| |
| Set the router address of the |
| |
Default | default gateway where the GOT is | 0.0.0.0 to | |
connected.(Only for connection via | |||
Gateway | 255.255.255.255 | ||
router) | |||
|
| ||
| (Default: 0.0.0.0) |
| |
|
|
| |
|
| 1024 to 5010 to | |
Ethernet | Set the GOT port No. for Ethernet | 5014 to 65534 | |
Download Port | download. | (Except for 5011, | |
No. | (Default: 5014) | 5012, 5013 and | |
|
| 49153) | |
|
|
| |
| Set the GOT port No. for the | 1024 to 5010 to | |
GOT | 5014 to 65534 | ||
connection with the Ethernet | |||
Communication | (Except for 5011, | ||
Port No. | module. | 5012, 5013 and | |
(Default: 5001) | |||
| 49153) | ||
|
| ||
|
|
| |
| Set the number of retries to be |
| |
| performed when a communication |
| |
| timeout occurs. |
| |
Retry | When receiving no response after | 0 to 5times | |
| retries, the communication times |
| |
| out. |
| |
| (Default: 3times) |
| |
|
|
| |
| Specify the time period from the |
| |
Startup Time | GOT startup until GOT starts the | 3 to 255sec | |
communication with the PLC CPU. | |||
|
| ||
| (Default: 3sec) |
| |
|
|
| |
| Set the time period for a |
| |
Timeout Time | communication to time out. | 3 to 90sec | |
| (Default: 3sec) |
| |
|
|
| |
| Set the delay time for reducing the |
| |
Delay Time | load of the network/destination | 0 to 10000 | |
PLC. | ( 10ms) | ||
| |||
| (Default: 0ms) |
| |
|
|
|
POINT
(1)Communication interface setting by Utility The communication interface setting can be changed on the Utility's [Communication Settings] after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GT User's Manual
(2)Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
18 - 12 | 18. CNC CONNECTION |
| 18.4 GOT Side Settings |