(b) Station information setting

 

 

Setting

Item*1

Set value

necessity at

GOT

 

 

 

 

connection

Station type

Ver.2 intelligent device

 

station (fixed)

 

 

 

 

 

 

Expanded cyclic setting*2

Single

 

Exclusive station count*2

Exclusive station 1

 

Remote station points

32 points (fixed)

 

 

 

 

Reserve/invalid station select

No setting

 

 

 

 

Intelligent buffer select (word)

(Use default value)

 

 

 

 

: Necessary : As necessary

: Not necessary

*1 When the [Mode] of the CC-Link module is set at [Remote net - (Ver. 2 mode)], [Remote station points] can be set. [Remote station points] is a setting for the remote I/O station. The default value (32 points) must be used on the GOT.

*2 Set the same setting as that of the GOT.

POINT

When changing the network parameter

After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF and then ON or resetting.

Parameter setting (when connecting to C Controller module)

Use SW3PVC-CCPU-E Ver.3.05F or later for the CC- Link utility.

(1) Connection settings

 

 

Setting

Item

Set value

necessity at

 

 

GOT connection

Target module*1

192.168.3.3 (Default)

 

Write authority

Mark the checkbox

 

 

 

 

User name*2

target

 

Password*2

password

 

Detailed settings

-

 

 

 

 

: Necessary : As necessary : Not necessary

*1 If the IP address of the C Controller module has been changed, input the changed IP address or host name.

*2 If the account of the C Controller module has been changed, input the changed user name and password.

13 - 18

13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

 

13.4 PLC Side Setting