Set each station number so that no station number overlaps.
The station number can be set without regard to the cable connection order. There is no problem even if station numbers are not consecutive.
Station | Station | Station | Station | Station |
No.3 | No.0 | No.1 | No.21 | No.6 |
GOT
Examples of station number setting
(1)Direct specification
When setting the device, specify the station number of the inverter of which data is to be changed.
Specification range
0 to 31
(2)Indirect specification
When setting the device, indirectly specify the station number of the inverter of which data is to be changed using the
When specifying the station No. from 100 to 155 on GT Designer3, the value of GD10 to GD25 compatible to the station No. specification will be the station No. of the inverter.
Specification | Compatible | Setting range | |
station NO. | device | ||
| |||
100 | GD10 |
| |
|
|
| |
101 | GD11 |
| |
|
|
| |
102 | GD12 |
| |
|
|
| |
103 | GD13 |
| |
|
|
| |
104 | GD14 |
| |
|
|
| |
105 | GD15 |
| |
|
|
| |
106 | GD16 | 0 to 31 | |
|
| ||
107 | GD17 | ||
For the setting other than the above, | |||
|
| ||
108 | GD18 | error (dedicated device is out of range) | |
will occur. | |||
|
| ||
109 | GD19 | ||
| |||
|
|
| |
110 | GD20 |
| |
|
|
| |
111 | GD21 |
| |
|
|
| |
112 | GD22 |
| |
|
|
| |
113 | GD23 |
| |
|
|
| |
114 | GD24 |
| |
|
|
| |
115 | GD25 |
| |
|
|
|