15.5.3Connecting FREQROL-F500, F500L series

Communication settings

Make the communication settings of the inverter.

Be sure to perform the inverter reset after updating each parameter.

(1) Communication port and corresponding parameters

GOT connection destination

Parameters corresponding to inverter

PU connector

Pr.79, Pr.117 to Pr.124

 

 

FR-A5NR (Option unit)

Pr.79, Pr.331 to Pr.337, Pr.340 to Pr.342

 

 

(2)Communication settings of inverter

Set the following parameters using the PU (parameter unit). Set Pr.160 (user group read selection) to 0 [All parameters can be accessed for reading and writing.] before making the parameter settings.

Do not change these parameters, even though they can be monitored from the GOT. If they are changed, communication with the GOT is disabled.

Setting item*1

Parameter No.

Set value

 

 

Contents of setting

PU connector

 

FR-A5NR

 

 

 

 

 

 

 

 

 

Communication station number

Pr.117

 

Pr.331

0 to 31

 

 

15.5.12 Station number

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication speed*2

Pr.118

 

Pr.332

192*4

 

 

 

19200bps

Stop bit length/data length

Pr.119

 

Pr.333

10

 

 

 

Data length: 7bit

Stop bit length*2

 

 

 

 

Stop bit length: 1bit

 

 

 

 

 

 

 

Parity check presence/absence*2

Pr.120

 

Pr.334

1

 

 

 

Odd

Number of communication retries

Pr.121

 

Pr.335

9999

 

 

The inverter will not come to an

 

 

 

 

alarm stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication check time interval

Pr.122

 

Pr.336

9999

 

 

 

Communication check

 

 

 

 

suspension

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wait time setting

Pr.123

 

Pr.337

0

 

 

 

0ms

 

 

 

 

 

 

 

 

 

CRLF presence/ absence selection

Pr.124

 

Pr.341

1*3

 

 

 

With CR, without LF

Protocol selection*5

 

 

 

 

 

 

 

PU

 

1

 

PU operation mode

 

 

 

 

connector

 

 

Operation mode selection

Pr.79

 

 

 

 

 

 

 

 

 

 

 

 

FR-A5NR

 

0*3

 

External operation mode at

 

 

 

 

 

 

 

 

 

 

 

 

power on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Link start mode selection*6

 

Pr.340

1

 

 

 

Computer link operation

E2PROM write selection*6

 

Pr.342

0*3

 

 

 

Written to RAM and EEPROM

*1 Setting items are parameter names described in the manual of FREQROL-F500 and F500L series.

*2 Settings on the GOT can be changed.

When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.

*3 Inverter default values (No need to change)

*4 Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.

*5 There is no Protocol selection setting on the inverter side.

*6 The setting is required on the inverter side when FR-A5NR is used.

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

15. INVERTER CONNECTION

15 - 33

15.5 FREQROL Series Inverter Side Settings