Parameter settings (Connection to MELSEC- Q, QS series) of System configuration1 (Network Type: CC IE Control)

(1)[Network parameter] of GX Developer

(a)Network parameter

 

 

 

 

Setting

Item

 

 

Set value

necessity at

 

 

GOT

 

 

 

 

 

 

 

 

connection

Network type

 

 

CC IE Control

 

 

(Control station) (fixed)

 

 

 

 

 

 

 

 

 

Starting I/O No.*1

 

 

0000H

 

Network No.*2

 

 

1

 

Total stations

 

 

2

 

 

 

 

 

 

Group No.

 

 

0 (fixed)

 

 

 

 

 

 

Station No.

 

 

1

 

 

 

 

 

 

Mode*3

 

 

Online

 

Network range assignment

 

Refer to (b)

 

 

 

 

 

 

Refresh parameters

 

 

 

 

 

 

 

 

 

Interrupt settings

 

(Use default value)

 

 

 

 

Interlink transmission

 

 

 

 

parameters

 

 

 

 

 

 

 

 

 

Routing parameters

 

 

Refer to (c)

 

 

 

 

 

 

 

: Necessary

: As necessary : Not necessary

*1 When using Q170MCPU, set it according to the system configuration.

*2 Specify the same network No. as that of the GOT.

*3 Set the same mode setting as that of the GOT.

(b) Network range assignment

 

 

 

 

 

 

 

Setting

 

Item

 

 

 

Set value

necessity at

 

 

 

 

GOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

Monitoring time

 

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

 

Station

 

Start

0000H

 

 

LB

 

No.1

 

End

00FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Station

 

Start

0100H

 

 

 

 

 

 

LB/LW

 

 

No.2

 

End

01FFH

 

setting(1)

 

 

 

 

 

 

 

 

 

Station

 

Start

00000H

 

*1

 

 

 

 

 

LW

 

No.1

 

End

000FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Station

 

Start

00100H

 

 

 

 

 

 

 

 

 

No.2

 

End

001FFH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LX/LY setting*1

 

 

 

No setting

 

Specify I/O master station*1

 

No setting

 

Specify reserved station

 

No setting

 

 

 

 

 

Supplementary setting

 

(Use default value)

 

 

 

 

 

 

 

 

 

: Necessary : As necessary : Not necessary *1 Be sure to set it to perform the cyclic transmission.

POINT

When changing the network parameter

After writing the network parameter to the PLC CPU, operate the PLC CPU ether turning OFF and then ON or resetting.

9

TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)

10

MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)

11

CC-Link IE CONTROLLER NETWORK CONNECTION

12

CC-Link IE FIELD NETWORK CONNECTION

13

CC-Link CONNECTION (INTELLIGENT DEVICE STATION)

14

CC-Link CONNECTION (Via G4)

15

CONNECTION

INVERTER

16

CONNECTION

SERVO AMPLIFIER

11. CC-Link IE CONTROLLER NETWORK CONNECTION

11 - 11

11.4 PLC Side Setting