Item

Description

Range

Monitor Speed

Set the monitor speed of the GOT.

High*1

This setting is not valid in all systems.

Normal

(GT16 only)

(Default: Normal)

Low*2

 

*1 This is effective when collecting a large data on other than the monitor screen (logging, recipe function, etc.). However, when connecting to Q00J/Q00/Q01CPU, the sequence scan time may be influenced. If you want to avoid the influence on the sequence scan time, do not set "High".

(High performance is hardly affected)

*2 Set this item if you want to avoid the influence on the sequence scan time further than the "Normal" setting when connecting to Q00J/Q00/Q01CPU. However, the monitor speed may be reduced.

*3 Refer to the following POINT.

POINT

Setting [Format]

This setting is required for replacement of F900 series with GOT1000 series.

(1)To change the communication settings of the serial communication module which is connected to F900, set as follows.

The value of Transmission Speed can be set to 115200bps.

(a)[Intelligent function module switch setting] of

PLC

Switch No.

CH1 side

CH2 side

Switch 1

0000H

-

 

 

 

Switch 2

0000H

-

 

 

 

Switch 3

-

0000H

 

 

 

Switch 4

-

0000H

 

 

 

Switch 5

0000H

0000H

 

 

 

7.5 PLC Side Setting

(b) GOT communication settings

Format

1

(2)To maintain the communication settings of the serial communication module which is connected to F900, set the communication setting of the GOT as follows.

The value of Transmission Speed remains 38400bps.

 

Format

Transmission Speed

 

 

2

38400bps

 

 

 

 

 

(2) AJ71QC24, MELDAS C6*

Item

Description

Range

 

 

4800bps,

 

Set this item when change the

9600bps,

Transmission

transmission speed used for

19200bps,

Speed

communication with the connected

38400bps,

 

equipment. (Default: 19200bps)

57600bps,

 

 

115200bps

 

 

 

 

Set this item when change the data

 

Data Bit

length used for communication with the

8bit (fixed)

connected equipment.

 

 

 

(Default: 8bit)

 

 

 

 

 

Specify the stop bit length for

 

Stop Bit

communications.

1bit (fixed)

 

(Default: 1bit)

 

 

 

 

 

Specify whether or not to perform a

 

Parity

parity check, and how it is performed

Odd (fixed)

during communication.

 

 

 

(Default: Odd)

 

 

 

 

 

Set the number of retries to be

 

 

performed when a communication

 

Retry

timeout occurs. When receiving no

0 to 5times

response after retries, the

 

 

 

communication times out.

 

 

(Default: 0time)

 

 

 

 

Timeout Time

Set the time period for a communication

3 to 30sec

to time out. (Default: 3sec)

 

 

 

 

 

 

Set this item to adjust the transmission

 

Delay Time

timing of the communication request

0 to 300 (ms)

 

from the GOT. (Default: 0ms)

 

7 - 20

7. COMPUTER LINK CONNECTION

 

7.4 GOT Side Settings