Item | Description | Range | |
Monitor Speed | Set the monitor speed of the GOT. | High*1 | |
This setting is not valid in all systems. | Normal | ||
(GT16 only) | |||
(Default: Normal) | Low*2 | ||
|
*1 This is effective when collecting a large data on other than the monitor screen (logging, recipe function, etc.). However, when connecting to Q00J/Q00/Q01CPU, the sequence scan time may be influenced. If you want to avoid the influence on the sequence scan time, do not set "High".
(High performance is hardly affected)
*2 Set this item if you want to avoid the influence on the sequence scan time further than the "Normal" setting when connecting to Q00J/Q00/Q01CPU. However, the monitor speed may be reduced.
*3 Refer to the following POINT.
POINT
Setting [Format]
This setting is required for replacement of F900 series with GOT1000 series.
(1)To change the communication settings of the serial communication module which is connected to F900, set as follows.
The value of Transmission Speed can be set to 115200bps.
(a)[Intelligent function module switch setting] of
PLC
Switch No. | CH1 side | CH2 side |
Switch 1 | 0000H | - |
|
|
|
Switch 2 | 0000H | - |
|
|
|
Switch 3 | - | 0000H |
|
|
|
Switch 4 | - | 0000H |
|
|
|
Switch 5 | 0000H | 0000H |
|
|
|
(b) GOT communication settings
Format
1
(2)To maintain the communication settings of the serial communication module which is connected to F900, set the communication setting of the GOT as follows.
The value of Transmission Speed remains 38400bps.
| Format | Transmission Speed |
|
| 2 | 38400bps |
|
|
|
|
|
(2) AJ71QC24, MELDAS C6*
Item | Description | Range | |
|
| 4800bps, | |
| Set this item when change the | 9600bps, | |
Transmission | transmission speed used for | 19200bps, | |
Speed | communication with the connected | 38400bps, | |
| equipment. (Default: 19200bps) | 57600bps, | |
|
| 115200bps | |
|
|
| |
| Set this item when change the data |
| |
Data Bit | length used for communication with the | 8bit (fixed) | |
connected equipment. | |||
|
| ||
| (Default: 8bit) |
| |
|
|
| |
| Specify the stop bit length for |
| |
Stop Bit | communications. | 1bit (fixed) | |
| (Default: 1bit) |
| |
|
|
| |
| Specify whether or not to perform a |
| |
Parity | parity check, and how it is performed | Odd (fixed) | |
during communication. | |||
|
| ||
| (Default: Odd) |
| |
|
|
| |
| Set the number of retries to be |
| |
| performed when a communication |
| |
Retry | timeout occurs. When receiving no | 0 to 5times | |
response after retries, the | |||
|
| ||
| communication times out. |
| |
| (Default: 0time) |
| |
|
|
| |
Timeout Time | Set the time period for a communication | 3 to 30sec | |
to time out. (Default: 3sec) | |||
|
| ||
|
|
| |
| Set this item to adjust the transmission |
| |
Delay Time | timing of the communication request | 0 to 300 (ms) | |
| from the GOT. (Default: 0ms) |
|
7 - 20 | 7. COMPUTER LINK CONNECTION |
| 7.4 GOT Side Settings |