8.3 GOT Side Settings
1
Set the channel of the connected equipment.
2.
3.
4.
Click!
1. Select [Common] [Controller Setting] from the menu.
2. The Controller Setting window is displayed. Select the channel to be used from the list menu.
3. Set the following items.
•Manufacturer: Mitsubishi
•Controller Type: Set according to the Controller Type to be connected.
•I/F: Interface to be used
•Driver:
Ethernet(MELSEC), Q17nNC,
4.The detailed setting is displayed after Manufacturer, Controller Type, I/F, and Driver are set.
Make the settings according to the usage environment.
8.3.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
The settings of connecting equipment can be confirmed in [I/F Communication Setting].
For details, refer to the following. 1.1.2 I/F communication setting
Make the settings according to the usage environment.
GT16, GT14
Item | Description | Range | |
GOT NET No. | Set the network No. of the GOT. | 1 to 239 | |
(Default: 1) | |||
|
| ||
|
|
| |
GOT PLC No. | Set the station No. of the GOT. | 1 to 64 | |
(Default: 1) | |||
|
| ||
|
|
| |
GOT | Set the IP address of the GOT. | 0.0.0.0 to | |
IP Address*2 | (Default: 192.168.3.18) | 255.255.255.255 | |
| Set the subnet mask for the sub |
| |
| network. (Only for connection via |
| |
Subnet Mask*2 | router) | 0.0.0.0 to | |
If the sub network is not used, the | 255.255.255.255 | ||
| |||
| default value is set. |
| |
| (Default: 255.255.255.0) |
| |
|
|
| |
Default | Set the router address of the default |
| |
gateway where the GOT is connected. | 0.0.0.0 to | ||
Gateway*2 | (Only for connection via router) | 255.255.255.255 | |
| (Default: 0.0.0.0) |
| |
|
|
| |
Ethernet | Set the GOT port No. for Ethernet | 1024 to 5010, | |
5014 to 65534 | |||
Download Port | download. | ||
(Except for 5011, 5012, | |||
No.*2 | (Default: 5014) | ||
5013 and 49153) | |||
|
| ||
|
|
| |
| Set the GOT port No. for the |
| |
| connection with the Ethernet module. | 1024 to 5010, | |
GOT | • For Ethernet (MELSEC), Q17nNC, | ||
5014 to 65534 | |||
Communication | and | ||
(Except for 5011, 5012, | |||
Port No. | (Default: 5001) | ||
5013 and 49153) | |||
| • For Ethernet(FX), Gateway | ||
|
| ||
| (Default: 5019) |
| |
|
|
| |
| Set the number of retries to be |
| |
| performed when a communication |
| |
Retry | timeout occurs. | 0 to 5times | |
When receiving no response after | |||
|
| ||
| retries, the communication times out. |
| |
| (Default: 3times) |
| |
|
|
| |
| Specify the time period from the GOT |
| |
Startup Time | startup until GOT starts the | 3 to 255sec | |
communication with the PLC CPU. | |||
|
| ||
| (Default: 3sec) |
| |
|
|
| |
Timeout Time | Set the time period for a |
| |
communication to time out. | 1 to 90sec | ||
*1 | |||
(Default: 3sec) |
| ||
|
| ||
|
|
| |
| Set the delay time for reducing the | 0 to 10000 | |
Delay Time | load of the network/destination PLC. | ||
( 10ms) | |||
| (Default: 0ms) | ||
|
| ||
|
|
|
PREPARATORYFORPROCEDURESMONITORING 2
RANGESETBE
DEVICE CANTHAT 3
RANGEACCESS MONITORINGFOR 4
MONITORTOREDUNTANTSYSTEM HOW 5
CONNECTIONBUS 6
DIRECTTOCONNECTIONCPU 7
LINKCOMPUTER CONNECTION 8
ETHERNETCONNECTION
8. ETHERNET CONNECTION | 8 - 15 |
8.3 GOT Side Settings |
|