8.4.9Connecting to CC-Link IE Field Network Ethernet Adapter Module

This section describes the settings of the GOT, Ethernet adapter module and the PLC in the following system configuration.

System configuration

<GOT>

(Use default value for settings other than the following.)

Network No.

:3 *1

PC No.

:1

IP address

:192.168.3.18

Port No.

:5001

Communication :UDP (fixed) format

Ethernet

<Ethernet adapter module>

(Use default value for settings other than the following.)

Ethernet setting

:192.168.3.30

IP address

CC-Link IE Field Network setting

Network No.

:1

Station No.

:1

CC-Link IE Field Network

HUB

*2

<CC-Link IE Field Network Master/Local module> (Use default value for settings other than the following.)

Network Type

: CC IE Field (Master station)

Network No.

: 1

PC No.

: 0

Total Stations

: 2

 

*2

<CC-Link IE Field Network Master/Local module> (Use default value for settings other than the following.)

Network Type

: CC IE Field (Local station)

Network No.

: 1

PC No.

: 2

*1 Set the GOT network No. according to the third octet (network No.) of the Ethernet adapter module IP address.

*2 The CC-Link IE Field Network Master/Local module is mounted on slot 0 of the base unit.

The start I/O No. of the CC-Link IE Field Network Master/ Local module is set at [0].

GX Works2 network parameter Ethernet/CC IE/MELSECNET

For details of the setting contents of PLC side, refer to the following manual.

MELSEC-Q CC-Link IE Field Network Master/ Local Module User's Manual

(1)Network Type, Network No., Total Stations setting Example: Master station setting

Item

Set value

Master station

Local station

 

Network type

CC IE Field

CC IE Field

(Master station)

(Local station)

 

 

 

 

Network No.

1

1

 

 

 

Total Stations

2

-

 

 

 

Station No.

0 (fixed)

2

 

 

 

(2)Routing parameter setting

Set the followings as necessary.

Up to 64 [Transfer Network No.]s can be set. However, the same transfer network number cannot be set twice or more (multiple times).

Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.

Item

Range

Transfer Network No.

1 to 239

 

 

Relay Network No.

1 to 239

 

 

Relay Station No.

1 to 64

 

 

8 - 44

8. ETHERNET CONNECTION

 

8.4 PLC Side Setting