This section describes the settings of the GOT, Ethernet adapter module and the PLC in the following system configuration.
System configuration
<GOT>
(Use default value for settings other than the following.)
Network No. | :3 *1 |
PC No. | :1 |
IP address | :192.168.3.18 |
Port No. | :5001 |
Communication :UDP (fixed) format
Ethernet
<Ethernet adapter module>
(Use default value for settings other than the following.)
Ethernet setting | :192.168.3.30 |
IP address |
Network No. | :1 |
Station No. | :1 |
HUB
*2
Network Type | : CC IE Field (Master station) |
Network No. | : 1 |
PC No. | : 0 |
Total Stations | : 2 |
| *2 |
Network Type | : CC IE Field (Local station) |
Network No. | : 1 |
PC No. | : 2 |
*1 Set the GOT network No. according to the third octet (network No.) of the Ethernet adapter module IP address.
*2 The
The start I/O No. of the
GX Works2 network parameter Ethernet/CC IE/MELSECNET
For details of the setting contents of PLC side, refer to the following manual.
(1)Network Type, Network No., Total Stations setting Example: Master station setting
Item | Set value | ||
Master station | Local station | ||
| |||
Network type | CC IE Field | CC IE Field | |
(Master station) | (Local station) | ||
| |||
|
|
| |
Network No. | 1 | 1 | |
|
|
| |
Total Stations | 2 | - | |
|
|
| |
Station No. | 0 (fixed) | 2 | |
|
|
|
(2)Routing parameter setting
Set the followings as necessary.
Up to 64 [Transfer Network No.]s can be set. However, the same transfer network number cannot be set twice or more (multiple times).
Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.
Item | Range |
Transfer Network No. | 1 to 239 |
|
|
Relay Network No. | 1 to 239 |
|
|
Relay Station No. | 1 to 64 |
|
|
8 - 44 | 8. ETHERNET CONNECTION |
| 8.4 PLC Side Setting |