4.7 Ethernet Connection

This section explains the Ethernet connection that connects the GOT to the Ethernet network system. The following shows an example of connecting the GOT to the Ethernet network.

 

 

 

 

 

 

 

 

Network No. 1, Station No. 3

 

 

 

 

 

GOT

 

 

 

 

 

 

 

 

 

 

Network No. 1, Station No. 1

 

 

 

 

 

Ethernet

 

 

 

 

 

 

 

 

 

 

 

 

 

Monitor target

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module

supplyPower

Q25PRHCPU

 

25-QJ71LP21

QJ71BR11

100-QJ71E71

 

QJ61BT11N

 

Empt

 

module

supplyPower

 

Q25PRHCPU

 

 

25-QJ71LP21

QJ71BR11

100-QJ71E71

Control

 

 

 

 

 

 

 

system

 

 

 

 

y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(System A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MELSECNET/H remote I/O network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module

supply Power

 

25-QJ72LP25

QJ71C24N

 

Empt

 

 

Empt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y

 

 

y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)Connection method

Connect the Ethernet network system to the GOT. For details, refer to the following.

Network No. 1,

Station No. 2

QJ61BT11N

Empt

Standby

y

 

 

 

 

system

 

 

(System B)

8. ETHERNET CONNECTION

(2)GT Designer3 setting

Set GT Designer3 as follows.

Setting item

Settings

Model

 

 

MELSEC-QnA/Q/QS, MELDAS C6*

 

Controller Type

 

 

 

 

 

MELSEC-QnA/Q, MELDAS C6*

 

 

 

Other (NW No. 1 (network No. of Ethernet),

 

Device setting

Other station

Station No. ** (** indicates the station number of the control system. Station No. 1,

 

(Network setting)

 

in the above example))

 

 

Host

Host

 

Q Redundant Setting

 

4.9 Q Redundant Setting

 

(3)Monitoring target change when system switching occurs in a redundant system

When system switching occurs, Ethernet module station No. 2 takes over the control of the Ethernet network system as the control system.

Since the GOT monitors the control system, he monitoring target is automatically changed to the Ethernet module station No. 2.

POINT

When monitoring control system without Q redundant setting (Only GT16, GT15 and GT14)

When system switching occurs, Ethernet module station No. 2 takes over the control of the Ethernet network system as the control system.

Since the GOT monitors the station of the specified station number, the monitoring target cannot be changed to the station No. 2 in response to the system switching.

As a countermeasure, create a screen to monitor the PLC CPU of the control system by switching the station numbers between System A and System B using the script function.

4.10 Switch the Monitor Target to the Control System Using the Script Function

4 - 24

4. HOW TO MONITOR REDUNTANT SYSTEM

 