15.3 Connection Diagram
9
The following diagram shows the connection between the GOT and the inverter.
15.3.1Connection diagram
RS422 connection diagram 1)
(For GT16, GT15, GT14, GT12, GT11, GT105 , GT104 )
GOT side*1 | Inverter or Distributor side | ||||
(Modular connector) | |||||
RDA | 2 |
|
| 5 | SDA |
|
| ||||
RDB | 7 |
|
| 4 | SDB |
|
| ||||
SDA | 1 |
|
| 3 | RDA |
|
| ||||
SDB | 6 |
|
| 6 | RDB |
|
| ||||
RSA | 3 |
|
| 2 | P5S |
RSB | 8 |
|
| 8 | P5S |
CSA | 4 |
|
| - | - |
CSB | 9 |
|
| - | - |
SG | 5 |
|
| 1 | SG |
|
| ||||
FG | - |
|
|
|
|
|
|
|
|
|
|
*1 For GT16, GT15 and GT12, set the terminating resistor to "Disable".
For GT14, GT11 and GT10, set the terminating resistor to "330 ".
1.4.3 Terminating resistors of GOT
RS422 connection diagram 2)
(For GT16, GT15, GT14, GT12, GT11, GT105 , GT104 )
GOT side*2 | |||||
(terminal block) | |||||
RDA | 2 |
|
|
| SDA |
|
|
| |||
RDB | 7 |
|
|
| SDB |
|
|
| |||
SDA | 1 |
|
|
| RDA |
|
|
| |||
SDB | 6 |
|
|
| RDB |
| *1 |
| |||
|
|
|
|
| |
RSA | 3 |
|
|
| RDR |
RSB | 8 |
|
|
|
|
CSA | 4 |
|
|
|
|
CSB | 9 |
|
|
|
|
SG | 5 |
|
|
| SG |
|
|
| |||
FG | - |
|
|
|
|
|
|
|
|
|
|
*1 Connect a terminating resistor jumper to RDB and RDR.The terminating resister jumper is packed together with the
*2 For GT16, GT15 and GT12, set the terminating resistor to "Disable".
For GT14, GT11 and GT10, set the terminating resistor to "330 ".
RS422 connection diagram 3)
Distributor side | Inverter side or distributor side | ||||
(Modular connector) | (Modular connector) | ||||
SDA |
|
|
|
| SDA |
5 |
|
| 5 | ||
|
| ||||
SDB | 4 |
|
| 4 | SDB |
|
| ||||
RDA | 3 |
|
| 3 | RDA |
|
| ||||
RDB | 6 |
|
| 6 | RDB |
|
| ||||
P5S | 2 |
|
| 2 | P5S |
P5S | 8 |
|
| 8 | P5S |
SG | 1 |
|
| 1 | SG |
|
| ||||
|
|
|
|
|
|
TO CONNECTIONPLC MELSECNET/H(PLCNETWORK)
10
MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
11
12
13
14
15
CONNECTION
INVERTER
16
CONNECTION
SERVO AMPLIFIER
15. INVERTER CONNECTION | 15 - 21 |
15.3 Connection Diagram |
|