(1) Controller setting

Item

Set value (Use default value)

GOT NET No.

1

 

 

GOT PLC No.

1

 

 

GOT IP Address

192.168.3.18

 

 

GOT Port No. (Communication)

5001

 

 

GOT Port No.

5014

(Ethernet Download)

 

 

 

Default Gateway

0.0.0.0

 

 

Subnet Mask

255.255.255.0

 

 

Retry

3times

 

 

Startup Time

3sec

 

 

Timeout Time

3sec

 

 

Delay Time

0ms

 

 

(2) Ethernet setting

 

Item

 

 

Set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Host

*

 

-

 

 

 

 

 

 

 

 

 

 

 

 

N/W No.

1*1

1*1

Ethernet setting

PLC No.

2*2

3*2

Type

QnD(H)CCPU

QnD(H)CCPU

No.1

 

 

 

 

 

 

 

 

 

 

 

IP address

192.168.3.1

192.168.3.2

 

 

 

 

 

 

 

 

 

 

 

Port No.

5006 (fixed)

5006 (fixed)

 

 

 

 

 

 

 

 

 

 

 

Communication

UDP (fixed)

UDP (fixed)

 

 

 

 

 

 

 

 

 

*1 Set the same value as that of GOT N/W No.

*2 Set a value different from that of the GOT PLC No. and the PLC No. of other PLCs on the same network.

Checking communication state of C Controller module

(1)When using the Command Prompt of Windows®. Execute a Ping command at the Command Prompt of Windows®.

(a)When normal communication C:\>Ping 192.168.0.1

Reply from 192.168.0.1: bytes=32 time <10ms TTL=32

(b)When abnormal communication C:\>Ping 192.168.0.1 Request timed out.

(2)When abnormal communication

At abnormal communication, check the followings and execute the Ping command again.

• Cable connecting condition

• Confirmation of switch and network parameter setting

• Operation state of PLC CPU (faulty or not)

• The IP address of C Controller module specified in the ping command

8.4.5Connecting to Ethernet module (QnA Series)

This section describes the settings of the GOT and Ethernet module (QnA Series) in the following case of the system configuration.

POINT

Ethernet module (QnA Series)

For details of the Ethernet module (QnA Series), refer to the following manual.

For QnA Ethernet Interface Module User’s Manual

System configuration

[Controller Setting] and [Ethernet] of GT

Designer3

<GOT>(The settings other than the following are set to the default)

Network No.

: 1

PLC No.

: 1

IP address

: 192.168.0.18

Port No.

: 5001

Communication format : UDP(fixed)

<Ethernet module>*1(The settings other than the following are set to the default)

Network No.

: 1

PLC No.

: 2

IP address

: 192.168.0.19

Port No.

: 5001

Communication format

: UDP(fixed)

Switch settings of Ethernet module

[Network parameter] of GX Developer

*1 The Ethernet module is mounted on the base unit slot 0. The Start I/O No. of the Ethernet module is set to "0".

8 - 30

8. ETHERNET CONNECTION

 

8.4 PLC Side Setting