When the GOT is OFF, the following currents are supplied to the GOT from the PLC CPU side (the power supply module on the main base unit).(The GOT does not operate when it is OFF.)
Design the system so that the 5V DC current consumption of the modules on the main base unit and the total current consumption of the GOTs will not exceed the rated output current of 5V DC of the power supply module in use.
When connecting to | No. of GOTs | Total current | |
consumption | |||
|
| ||
| 5 | 2200mA | |
|
|
| |
When connecting to | 4 | 1760mA | |
|
| ||
3 | 1320mA | ||
QCPU (Q mode) | |||
|
| ||
2 | 880mA | ||
| |||
|
|
| |
| 1 | 440mA | |
|
|
| |
| 3 | 360mA | |
|
|
| |
Other than QCPU (Q mode) | 2 | 240mA | |
|
|
| |
| 1 | 120mA | |
|
|
|
Do not use the I/O signals assigned to the PLC CPU in sequence programs, as these signals are used by the GOT system.
When these signals are used, GOT functions cannot be assured.
5.4.10When connecting to a QCPU (Q mode)(1)Restrictions in overall cable length to No. of GOTs The following restrictions apply when 3 of more GOTs are connected:
Number | Overall Cable | Restriction | Overall Cable | Restriction | |
of GOTs | Length | Length | |||
|
| ||||
1 |
| (No restrictions) |
| ||
|
|
| |||
2 |
|
| |||
|
|
|
| ||
|
|
|
|
| |
3 | Less than |
| 25 to 37m | Use the same | |
25m |
| power supply for | |||
|
|
| |||
|
|
|
| the PLC and all | |
4 | Less than | (No | 20 to 37m | ||
GOTs, and turn | |||||
20m | restrictions) | ||||
|
| these devices | |||
| Less than |
|
| ||
5 |
| 15 to 37m | ON and OFF | ||
15m |
| simultaneously. | |||
|
|
| |||
|
|
|
|
|
(2)When using a Q00JCPU, Q00UJCPU
The bus extension connector box can be connected only to the extension base unit.
(Connecting it to the main base unit is not allowed)
Q00JCPU,
Q00UJCPU
(3)When using a Q00J/Q00UJ/Q00/Q00U/Q01/Q01U/ Q02UCPU
When a GOT is
When a GOT is
Main base unit
Q00JCPU, Q00UJCPU
Extension base unit Extension
stage 1
Stage No. setting connector
GOT
Stage No. :2
Main base unit
Q00CPU, Q00UCPU, Q01CPU,
Q01UCPU, Q02UCPU
Extension base unit Extension
stage 1
Extension stage 2
Extension stage 3
Stage No. setting connector
GOT
Stage No. :4
5 - 36 | 5. BUS CONNECTION |
| 5.4 Precautions |