POINT

(1)Example of [Ethernet setting]

For examples of [Ethernet setting], refer to the following.

8.4 PLC Side Setting

(2)Parameter reflection function of MELSOFT Navigator

(a)The color of the cells for the items which are reflected to GT Designer3 from MELSOFT Navigator changes to green. Set items, which are displayed in green cells, from the MELSOFT Navigator.

(b)When the settings of N/W No., PLC No., type or IP address are reflected to the parameter from the MELSOFT Navigator, those settings are added. Items set in advance are not deleted. However, if the combination of the N/ W No. and the PLC No. or the IP address overlaps, the item set in advance is overwritten.

(3)Changing the host on the GOT main unit

The host can be changed by the utility function of the GOT main unit. For the detailed connection method, refer to the following manual.

User's Manual of GOT used. (When using GT16)

8.3.4Routing parameter setting

Up to 64 [Transfer Network No.]s can be set.

However, the same transfer network number cannot be set twice or more (multiple times).

Therefore, the one that can access to other station from the request source host GOT is 64 kinds of [Transfer Network No.]s.

POINT

Routing parameter setting

When communicating within the host network, routing parameter setting is unnecessary.

For details of routing parameters, refer to the following manual.

Q Corresponding Ethernet Interface Module User's Manual (Application)

Item

Range

Transfer Network No.

1 to 239

 

 

Relay Network No.*1

1 to 239

Relay Station No.*1

1 to 64

*1 When accessing to other networks relaying a Build-in Ethernet port CPU, set the virtual network No. and PLC No. set in the Ethernet settings on GT Designer3.

8 - 18

8. ETHERNET CONNECTION

 

8.3 GOT Side Settings