(1) Station number setting switch
|
|
|
|
|
|
|
|
| Setting |
Station number setting | Description | Set | necessity at | ||||||
switch |
|
|
|
|
|
| value | GOT | |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| connection |
STATION NO. |
| 2 | 3 |
|
|
| Station number |
|
|
| 0 |
| 5 |
|
|
| |||
X10 | 1 |
|
| 4 |
|
|
|
| |
|
|
|
|
|
|
| |||
9 |
|
| 6 |
| setting | 1 |
| ||
|
| 8 | 7 |
|
|
| |||
|
|
|
|
|
|
| |||
| 1 | 2 | 3 | 4 |
| *1 |
|
| |
X1 | 0 |
|
|
| 5 |
| (Station No.1) |
|
|
9 | 7 | 6 |
|
|
|
| |||
|
| 8 |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
: Necessary : As necessary : Not necessary *1 Do not set the same station No. as that of the GOT.
(2) Mode setting switch
|
|
|
|
|
|
|
|
|
|
| Setting |
Mode setting switch |
| Description | Set | necessity at | |||||||
| value | GOT | |||||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| connection |
|
|
|
|
|
|
|
|
| Mode setting |
|
|
|
|
| 34 | 56 |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||
|
|
| 2 |
| 7 |
|
| (Online: |
|
| |
|
| 0 |
| 8 |
|
|
|
| |||
MODE | 1 |
|
|
| 9 |
|
|
| 0 |
| |
F |
| A |
|
|
|
| |||||
|
|
| E |
|
|
|
|
|
|
| |
|
|
| DC |
|
|
|
| 10Mbps)*2 |
|
| |
|
|
|
| B |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| : Necessary : As necessary | : Not necessary |
*2 Set the same mode setting and transmission speed as those of the GOT.
POINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
Connecting to
(1)[Network parameter] of GX Developer
(a)Network parameter
|
| Setting |
Item | Set value | necessity at |
|
| GOT connection |
| MNET/H mode |
|
Network type | (Control station) |
|
| (fixed) |
|
|
|
|
Starting I/O No.*1 | 0000H |
|
Network No.*2 | 1 |
|
Total stations | 2 |
|
|
|
|
Group No. | 0 (fixed) |
|
|
|
|
Mode*3 | Online |
|
Network range assignment | Refer to (b). |
|
|
|
|
Refresh parameters |
|
|
|
|
|
Interrupt settings |
|
|
|
|
|
Control station return setting | (Use default value) |
|
|
| |
Redundant settings*4 |
|
|
Interlink transmission |
|
|
parameters |
|
|
|
|
|
Routing parameters | Refer to (c). |
|
|
|
|
: Necessary : As necessary : Not necessary
*1 When using Q170MCPU, set it according to the system configuration.
*2 Specify the same network No. as that of the GOT.
*3 Set the same mode setting as that of the GOT.
*4 Set it when the MELSECNET/H network module is used in the redundant QnPRHCPU system.
9 - 12 | 9. MELSECNET/H CONNECTION (PLC TO PLC NETWORK) |