(3)Connecting the GOT and PLC in Ethernet connection

(a)Connecting to QCPU (Q mode)

1.

Click the Connection Destination view

 

[Connection Destination]

[(Connection target data

 

name)] in the Navigation window of GX Works2.

2.

The [Transfer Setup Connection1] is displayed.

3.

Set the [Transfer Setup Connection1]:

 

PC side I/F

: Serial USB

 

PLC side I/F

: GOT

 

Other Station Setting

: No Specification

4. Double-click [Serial USB] of the PC side I/F to display [PC side I/F Serial Setting].

5. Check-mark either of the following in [PC side I/F Serial Setting].

When connecting the GOT and PC with serial

Mark the [RS-232C] checkbox.

When connecting the GOT and PC with USB

Mark the [USB] checkbox.

6. Double-click [GOT] of the PLC side I/F to display [PLC side I/F Detailed Setting of GOT].

7. On the [PLC side I/F Detailed Setting of GOT], mark the [via GOT(Ethernet) transparent mode] checkbox and click [Setting...].

8. By clicking [Set], the [GOT (Ethernet) Transparent Setting] is displayed.

Here, set the built-in Ethernet port QCPU or Ethernet module, which is firstly connected via a GOT.

9. Set [QnUDE(H)] or [QJ71E71] for [PLC Type].