DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects

3-561DS1-BD (DS1 Interface Circuit Pack)

3
SAKI Sanity Test (#53)
This test is destructive. This test resets the circuit pack.
0 NO BOARD The test could not relate the internal ID to the port (no board).
This co uld be due t o incorre ct transl a tions, no board i s i nserte d, an inco r rect
board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the add ds1
UUCSS command to administer the DS1 interface if it is not already
administered.
2. If board was already administered correctly, check the error log to
determine if the board is hyperactive. If this is the case, the board is shut
down. Reseating the board will re-initialize the board.
3. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the lin kage between the internal ID and the port.
Table 3-237. TEST #53 SAKI Sanity Test
Error
Code Test Result Description/ Recommendation
None ABORT System resources required for this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005 ABORT Wrong circuit pack configuration to run this test. This error applies only to
DS1 Interface circuit packs. It means the DS1 Interface circuit pack is
providing timing for the system and, therefore, it cannot be reset without
major system disruptions.
1. If the circuit pack needs to be reset, then set synchronization to another
DS1 Interface circuit pack or to the Tone-Clock circuit pack and try
again. Refer to "SYNC (Synchronization)".
Continued on next page
Table 3-236. TEST #52 Control Channel Looparound Test — Continued
Error
Code Test Result Description/ Recommendation
Continued on next page