DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-1224UDS1-BD (UDS1 Interface Circuit Pack)
3
1 to 17 FAIL The test failed because the UDS1 interface circuit pack detected errors in the
received framing bits pattern. The error code equals the number of misframes
detected by the UDS1 interface circuit pack sinc e the last misframe alarm
inquiry test. Major bit and minor bit error rate (error types 2561 and 2817) error
logs often accompany misframe alarms. Clearing the cause of these error logs
may clear the misframes which a re occurring.
If the UDS1 connects to a T1 network facility or to another switch, do the
following:
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2. If the DS1 interface circuit pack is a TN464C, enter the list measurement
ds1-log UUCSS command to read the error seconds measurement.
3. Verify that both endpoints of the DS1 link are administered using the same
signaling mode, framing mode, and line coding .
4. Check the active alarm and error logs for recent alarms and errors against
the synchronization (SYNC). Follow the suggested repair procedure for
these errors.
5. Contact T1 Network Service or the technician at the remote switch to
diagnose the remote DS1 endpoint.
6. Check the physical connectivity of the UDS1 interface circuit p acks and the
cable.
7. Replace the local UDS1 interface circuit pack, and rep eat the test.
More information continues on the next page.
Table 3-526. TEST #145 Misframe Alarm Inquiry Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page